Electromechanical control unit
Counter gear mechanism for end positions OPEN and CLOSED
Limit switching
Single switches (1 NC and 1 NO) for each end position, not galvanically isolated
Standard:
Tandem switches (2 NC and 2 NO) for each end position, switches galvanically
isolated
Triple switches (3 NC and 3 NO) for each end position, switches galvanically
isolated
Intermediate position switch (DUO limit switching), adjustable for any position
Options:
Torque switching adjustable for directions OPEN and CLOSE
Torque switching
Single switches (1 NC and 1 NO) for each direction, not galvanically isolated
Standard:
Tandem switches (2 NC and 2 NO) for each direction, switches galvanically
isolated
Options:
Potentiometer or 0/4 – 20 mA (EWG/RWG)
Position feedback signal, ana-
logue (option)
Continuous indication, adjustable indicator disc with symbols OPEN and CLOSED
Mechanical position indicator
(option)
Blinker transmitter (option for modulating actuators)
Running indication
Self-regulating PTC heater, 5 – 20 W, 110 – 250 V AC/DC
Standard:
Heater in switch compartment
24 – 48 V AC/DC or 380 – 400 V AC
Options:
A resistance type heater of 5 W, 24 V AC is installed in the actuator in combination with AM
or AC actuator controls.
Technical data for limit and torque switches
2 x 10
6
starts
Mechanical lifetime
Silver plated contacts:
24 V AC/DC
U min.
250 V AC/DC
U max.
20 mA
I min.
5 A at 250 V (resistive load)
3 A at 250 V (inductive load, cos phi = 0.6)
I max. AC current
0.4 A at 250 V (resistive load)
0.03 A at 250 V (inductive load, L/R = 3 µs)
7 A at 30 V (resistive load)
5 A at 30 V (inductive load, L/R = 3 µs)
I max. DC current
Gold plated contacts
5 V
U min.
30 V
U max.
4 mA
I min.
400 mA
I max.
Technical data for blinker transmitter
10
7
starts
Mechanical lifetime
Silver plated contacts:
10 V AC/DC
U min.
250 V AC/DC
U max.
3 A at 250 V (resistive load)
2 A at 250 V (inductive load, cos phi
≈
0.8)
I max. AC current
0.25 A at 250 V (resistive load)
I max. DC current
Technical data for handwheel activation switches
10
6
starts
Mechanical lifetime
Silver plated contacts:
12 V DC
U min.
250 V AC
U max.
3 A at 250 V (inductive load, cos phi = 0.8)
I max. AC current
3 A at 12 V (resistive load)
I max. DC current
39
SQ 05.2 – SQ 14.2/SQR 05.2 – SQR 14.2
Technical data