41
Function Code 2:
The register details associated with the function code 2 (Read Input Status)
are as below.
DESCRIPTION
ADDRESS IN HEX
OPEN POSITION
0x0000
CLOSE POSITION
0x0001
SET POINT REACHED
0x0002
RUNNING OPEN
0x0004
RUNNING CLOSE
0x0005
THERMAL FAULT
0x0008
REMOTE SW POSITION
0x000A
LOCAL SW POSITION
0x000B
LSO
0x000C
LSC
0x000D
TSO
0x000E
TSC
0x000F
Note: The data values of the function code 2 is to be indicated in binary (1/0).
Function Code 4:
There are two registers present with the address 0x03E8 & 0x03E9 from
which the status details can be got. The details of the data associated with each address are
as tabulated below.
3.XMP-Version 1.0
3.XMP-Version 2.0
ADDRESS
0x3E8
0x3E9
0x3E8
0x3E9
0x3EA
DATA DETAILS
DATA DETAILS
BIT POSITION
DESCRIPTION
DESCRIPTION
0
LOCAL POSITION
TSC
LOCAL POSITION
TSC
Valve
Position
(0-1000)
1
REMOTE
POSITION
TSO
REMOTE POSITION
TSO
2
RUNNING OPEN
LSC
RUNNING OPEN
LSC
3
RUNNING CLOSE
LSO
RUNNING CLOSE
LSO
4
STOPPED
LOCAL POSITION
STOPPED
LOCAL POSITION
5
OPENED
POSITION
REMOTE POSITION
OPENED POSITION
REMOTE POSITION
6
CLOSED
POSITION
LOSS OF PHASE
CLOSED POSITION
LOSS OF PHASE
7
TSO
TH FAULT
TSO
TH FAULT
8
TSC
COMMON FAULT
TSC
COMMON FAULT
9
TH FAULT
PHASE REVERSE
TH FAULT
PHASE REVERSE
10
TOLR
RUNNING CLOSE
TOLR
RUNNING CLOSE
x
11
JAMMED VALVE
RUNNING OPEN
JAMMED VALVE
RUNNING OPEN
x
12
-
ESD-HARDWIRED
PHASE SEQ. ERROR
ESD-HARDWIRED
x
13
PHASE SEQ.
ERROR
SET POINT
REACHED
SET POINT
REACHED
SET POINT
REACHED
x
14
FAULT
CLOSED
FAULT
CLOSED
x
15
PROGRAM
MODE
OPENED
LCS ACTIVATED
OPENED
x