5.1.4 Power supply
The system will indicate a power failure in either of these situations:
Main power: A fault has occurred in the main power supply (AC power). If this fault
has occurred, check that the network power reaches the equipment. If so, check the
output of the AC / DC source, it should give 15V. In this case verify that the disconnect
switches are ON.
Redundant power: The equipment monitors the charger and the battery. It can register
failures related to these devices. To take this failures into account, it shoul be considered
that the battery has a shorter life time than the system.
If the battery is continuously discharged, the device will indicate a battery failure and
will not charge it until a minimum voltage level is reached in the battery. In the monitoring
menu you can see the current battery voltage. If this voltage is below 10.5V the battery
will not charge. To try to recover the battery you must use a specific charger and always
under supervision.
5.1.5 System
System will indicate a memory failure when a software execution or memory problem
occur. If after some restarts the problem persists, please notify support/reparations
service.
If a configuration loss occurs, system will enter in safe mode. In this mode default
factory configuration is used to avoid an unwanted emergency activation, but take note
that an inverted CIE configuration and connection will cause an activation if defaults are
restored.