Connection is made using female euroblock connectors given with the equipment. The

cable section range for each pole of this connector is: 0,14   1,5mm2 (30   14 AWG).

Inputs are activated when the dry contact is voltage free. (

N.O.= normally open

)

a) Zone emergency activation inputs

These   inputs   are   connected   the   same   way   as   the   general   entrance   to   allow   link

supervision.

Default function: When the input of one the zones Z1...Z6 is activated, the state of

general   emergency   will   get   activated  and   the   list  of   evacuation  messages   for   these
zones will start to be played. The rest of zones will play the list of alert messages that
can be configured in the configuration menu. 

If the contact is deactivated, the reproduction of the messages will be paused, but a

restart operation will be needed to go back to the inactivity mode or PA. 

b) General emergency activation input

Supervised   inputs   for   voltage-free   dry   contact   connection   (N.O.):   Restart   and

Emergency. 

So that the link can be supervised, the connection of the dry contact to the equipment

must   be   carried   out   by   means   of   two   external   10K   resistors   (supplied   with   the

Ω

equipment), placed at the output of the fire panel as indicated in the illustration 6. 

Function

: When the general emergency entrance (EMG) is activated by means of a

contact closure (0V), the equipment will automatically change from working mode to an
emergency state, and emitting the voice evacuation message through all zones of the
system. When the reset input (RST) is activated, the equipment will exit the emergency
operation mode and return to the idle state (PA).

It can be configured so the EMG input makes the combined function, it's called Auto-

reset. See b

NOTE: To avoid non-desired activation problems the system does not allow the alarm

activation   inputs   to   complete   the   sequence   EMG,   RST,   EMG   instantly.   The   second
consecutive activation will leave about 2 seconds of margin.

c) State output

These outputs are dry contacts that indicate if the equipment is in emergency or failure

state when they are closed. (

N.O.

)

6

Illustration 6: Fire Central Interface

Illustration 7: Supervised CIE connection

Summary of Contents for EN54-16

Page 1: ...User Manual EN54 16 and EN54 4 Voice Alarm and Public Address Certified System LDA ONE...

Page 2: ......

Page 3: ...Date and time 11 3 2 2 Evacuation messages Messages 11 3 2 3 Advanced mode question 12 3 3 Manual configuration Configuration 13 3 3 1 Audio Inputs 13 3 3 2 Audio Outputs 14 3 3 3 Speaker Line configu...

Page 4: ...og FLT_LOG FLT_Log 22 4 3 3 System log ERR_LOG SYS_Log 22 4 3 4 LOGs configuration Logs Config 22 4 3 5 System information Sys Info 22 4 3 6 Test 22 5 SYSTEM MAINTENANCE 23 5 1 FAILURE INDICATION RESO...

Page 5: ...ventilation 7 The equipment should only be opened by qualified or trained personnel 8 The equipment must be connected to an outlet with protective earthing 9 Pay attention to the connection polarity w...

Page 6: ...bution system for all types of installations Manual for FW version 01 00 04 01 onwards This user manual is valid for the following equipment and accessories of the series ONE 500 PA VA Central module...

Page 7: ...lenced by the button BACK c FLT FAULT Yellow On when the equipment is in failure state This indicator activates automatically after detecting failure in any of the supervised functions Simultaneously...

Page 8: ...tions Generally access levels allow to Level 1 L1 EN54 element visualization and use of PA System Level 2 L2 System management and emergency functions Password 0002 Level 3 L3 System configuration and...

Page 9: ...connectors of the ONE series are described The enclosure has 7 pre cut holes for the entry and exit of the wiring easily removed with a screwdriver Its size is 36mm which matches the size of the racor...

Page 10: ...in stand by and 8Ah for one hour in evacuation at maximum power With the recommended battery brand YUASA NP17 12I we have 17Ah enough to comply with stand by and evacuation needs Additionally a 25 Am...

Page 11: ...t the link can be supervised the connection of the dry contact to the equipment must be carried out by means of two external 10K resistors supplied with the equipment placed at the output of the fire...

Page 12: ...Zones 1 and 2 500W Zones 3 4 5 6 120W The connection is made by means of a 2 pin female euroblock connector and 5 08mm pitch supplied with the equipment The cable section range for each pole of this...

Page 13: ...igger for each dry contact or signal level with zone routing configuration Input level 1Vrms Balanced audio b 3 Input Configured as a background music input because it does not have activation trigger...

Page 14: ...3 contact Euroblock type connectors and 3 81 mm pass given with the equipment Cable section range for each pole of this connector is 0 14 1 5mm2 30 14 AWG The maximum output load is 10Kohm 2 2 9 Atten...

Page 15: ...port and export configurations or Logs c Expansion bay This connector us an expansion bay expected for future system ampliations Its future options will be to provide the simple or redundant Ethernet...

Page 16: ...Autosetup The automatic configuration function saves much of the configuration work of the ONE system The operation of the automatic configuration system makes the adjustments according to what is de...

Page 17: ...2 3 When it detects the end of line EOL devices the supervision of the general input and or the connected zone inputs will get activated If the EOL devices are not detected they will remain active wi...

Page 18: ...d consider that in Always on mode the source with higher priority will occupy all the zones where it is selected TTL Contact maneuver for dry contact normally opened VOX Enabled Noise gate switched in...

Page 19: ...tput has independent volume adjustment PA Volume VA Volume Mute Link to zone It configures the zones where it gets integrated to receive the same audio as this zone c VA Rec Out Recording output is as...

Page 20: ...r lines for each zone in case of a line failure A the zone will be still working thanks to the other speaker line B But maximum number of zones will be reduced to 3 for each ONE device This mode is en...

Page 21: ...Install It allows the user to install devices for their supervision MICs Config Parameter configuration Vumeter Indicates signal level in the common input only take into account when the device is ac...

Page 22: ...and 200 mOhms We recommend to adjust impedance according to the battery used For example for YUASA NP17 12I model we recommend 50mOhm a Battery charger Monitoring In order to help the user in the dia...

Page 23: ...will be visible in main Screen Date Time Edit system date and time 3 4 Login Access configuration Login submenu allows to introduce the password to use the system Otherways the user will be asked to i...

Page 24: ...r priority than the prerecorded messages 4 1 2 Enter EMG state Enter EMG Enter EMG option puts the system in emergency state deactivating PA Audio Sources except microphones but does not replay any ev...

Page 25: ...l inputs are activated at same time they will be automatically selected by the system following their priority level In this case Higher priority of these inputs is input 1 followed by input 2 interna...

Page 26: ...y the EN54 norm but that can be useful for system analysis With default configuration you only will see active errors to see faults history change the option See Solved FLT 4 3 4 LOGs configuration Lo...

Page 27: ...nu you can see the calibration measure established for each line In case of error at the time of calibration this number will be 0 or 9999 to indicate that the calibration is out of range If this faul...

Page 28: ...usly discharged the device will indicate a battery failure and will not charge it until a minimum voltage level is reached in the battery In the monitoring menu you can see the current battery voltage...

Page 29: ...45 female total 1000m Conectivity ACSI Link Preamplified Audio Outputs Attenuator Control Virtual m atrix Backup amplifiers 1 EN 54 16 backup amplifier with automatic priority Output power 500 W Pink...

Page 30: ...nnection failure indication 7 Voice alarm zones failure indication 8 Voice alarm manual control 9 External control devices interface 10 Redundant power amplifiers Auxiliar functions 1 Background music...

Page 31: ...nections are done close the cover Otherwise the unit will report a fault called intrusion detected 5 In the screen menu go to Configuration System pass 0003 Run Autosetup and press OK Rev 1 4 09 2019...

Reviews: