PROGRAMMABLE PARAMETERS
5I –
Starts per Hour
Range:
0 - 10
Default:
0
Description:
Sets the maximum number of starts the EMX4e will attempt in a
60 minute period. A setting of 0 disables this protection.
5J –
Phase Sequence
Options:
Any Sequence (default)
Positive Only
Negative Only
Description:
Selects which phase sequences the soft starter will allow at a
start. During its pre-start checks, the starter examines the
sequence of the phases at its input terminals and trips if the
actual sequence does not match the selected option.
9.8
6 Protection Action
6A –
Auto-Reset Count
Range:
0 – 5
Default:
0
Description:
Sets how many times the soft starter will auto-reset, if it
continues to trip.
The reset counter increases by one each time the soft starter
auto-resets, and resets after a successful start.
Setting 6A to zero disables auto-reset.
6B –
Auto-Reset Delay
Range:
0:05 - 15:00 (minutes:seconds) Default:
5 seconds
Description:
Sets a delay before the soft starter will auto-reset a trip.
6C –
Current Imbalance
Options:
Soft Trip and Log
(default)
The soft starter will stop the motor as
selected in parameter 2F
Stop Mode
, then
enter trip state. The trip must be reset
before the starter can restart.
Soft Trip and Reset The soft starter will stop the motor as
selected in parameter 2F
Stop Mode
, then
enter trip state. The trip will reset after the
auto-reset delay.
Trip Starter
The soft starter will remove power and the
motor will coast to stop. The trip must be
reset before the starter can restart.
62 |
EMX4e User Manual (710-18433-00C)