USER MANUAL
18
Modbus TCP Interface (710-14812-00D)
Register Description
Bits
Details
40618
Digital input state 0 to 15 For all inputs, 0 = open, 1 = closed (shorted)
0 = Start
1 = Stop
2 = Reset
3 = Input A
4 = Input B
5 = Input C, if fitted
6 = Input D, if fitted
7 to 15 =
Reserved
40619~
40631
Reserved
1
Refer to the relevant soft starter literature for a complete parameter list. The first
product parameter is always allocated to register 40009. The last product parameter is
allocated to register 40XXX, where XXX = 008 plus total number of available
parameters in the product. The Modbus TCP protocol limits read/write operations to a
maximum of 123 registers at one time. The registers must be consecutive. These
registers support multiple write (Modbus function code 16). Attempting to write to a
single register will return an error code 01 (Illegal function code).