background image

AUBER INSTRUMENTS

WWW.AUBERINS.COM

2013.11

P2/3

5. Parameter Settings

To change the target temperature or humidity , press SET key 
momentarily. The controller will show tSP (temperature set point), 
press SET again will show HSP (humidity set point). Use Up or Down 
key to change the tSP or HSP.

To change the other parmameters, press SET key for 5 seconds, the 
RH window will show tE or Hu (depending on which menu was set 
last time), press SET key to enter the set menu for temperature 
control or humidity control. Or press Down (or Up) key to change the 
RH (or Hu) window to Hu (or RH). Then press SET key to enter the 
set menu for humidity (or temperature) control.

To s et up the while in the parameter setup mode, use Up or Down 
key to modify the parameter value. Then press SET key to confirm 
the change. The instrument will automatically exit if no key is pressed 
for 10 seconds.  Please see the Table 1 for the parameters.

Description

Setting range

Initial Note

tSP

tSP

Temperature Set Point

-40~176 ºF

-40~80 ºC

75.0

HSP

HSP

Humidity Set Point

0~99.9 % RH

40.0

Edt

EDT

Set Menu Selection

TE: Temp Menu

Hu: Humidity Menu

TE

C-F

C-F

Temperature Unit

C: Celsius

F:Fahrenheit

F

tCM

tCM

Temperature Control Mode

Ht: Heating Control

CL: Cooling Control

CL

TdF

TDF

Temperature Control Differential

0~50.0

3.0

1

toF

toF

Temperature Calibration Offset

-10.0~10.0

0

2

tAH

TAH

Temperature High Limit Alarm

-40~176 ºF

-40~80 ºC

95.0

tAL

TAL

Temperature Low Limit Alarm

-40~176 ºF

-40~80 ºC

32.0

TAS

TAS

Temperature Anti-short Cycle 

Delay (only for cooling)

0~12 min

0

4

TSF

TSF

Temperature Sensor Failure 

Operation

on: Output energized

oFF:

Output de-energized

oFF

5

HCM

HCM

Humidity Control Mode

deH: Dehumidifying

H: Humidifying

deH

HdF

HDF

Humidity Control Differential

0~50.0

3.0

1

HoF

HoF

Humidity Calibation Offset

-10.0~10.0

0

2

HAH

HAH

Humidity High Limit Alarm

0~99.9

90.0

HAL

HAL

Humidity Low Limit Alarm

0~99.9

10.0

HAS

HAS

Humidity Anti-short Cycle 

Delay (only for dehumidifying)

0~12 min

0

4

HSF

oFF

Humididty Sensor Failure 

operation

on: Output energized

oFF:

Output de-energized

oFF

5

3

1

Code

3

Table 1. Parameters Description

Note 1. 

For heating (or humidifying), the output will be off when the 

temperature (or humidity) reaches the set point; will be on again 
when the temperature (or humidity) drops down to tSP-tdF (or HSP-
HdF).

For cooling (or dehumidi fying), the output will be off when the 
temperature (or humidity) reahes the set point; will be on again when  
the temperature (or humidity) rises to tSP+tdF (or HSP+HdF).

Small differential gives tight control; large differential reduces the 
frequency of cycle on and off. It will extend the life of relay and 
compressor.

Note 2. 

The offset is used to set an input offset to compensate the 

error produced by the sensor or input signal itself.
For example, for temperature, if the unit displays 37 ºF when the 
actual temperature is 32 ºF, setting parameter toF= - 5 will make the 
controller display 32  ºF.

Note 3. 

The low limit alarm will be always lower than the high limit 

alarm. When the measured temperature (humidity) is higher than tAH 
(HAH), the temperature (humidity) high limit alarm will be on; when 
the measured temperature (humidity) is lower than tAL (HAL), the 
temperature (humidity) low limit alarm will be on.

When alarm is on, the display will be flashing between the measured 
value and alarm type. To mute the alarm when it is on, press the 
Down key momentarily. When the alarm is muted, the alarm indicator 
(see F igure 1, the small dot on the last di git ) will be on. If the 
measured value gets out of the alarm zone then gets back to the 
alarm zone again, the alarm will be on again. To resume the alarm, 
press the Up key, the alarm indicator will be off. 

To disable the alarm, set High Limit Alarm= Low Limit Alarm.  

Note 4. 

When T he controller is used for cooling (or dehumidifying 

control)  and  load  is  a  compressor,  it  should  not  turn  on  the 
compressor  when  it  is  at  high  pressure  (just  after  turned  off). 
Otherwise,  It  may  shorten  the  life  of  compressor.  The  Anti-Short 
Cycle Delay function can be used to prevent the rapid cycling of the 
compressor.  It  establishes  the  minimum  time that the NO.  contacts 
remains open (after reaching cutout) before closing again. The delay 
overrides any Load Demand and does not allow the NO. contacts to 
close  until  the  set  time-delay  value  has  elapsed.  It  gives  time  to 
release the refrigerant pressure through evaporator. It is typically set 
to 4- 6 (minutes). 

Note 5. 

The TSF (HSF) can be set to ON or OFF. When it is set to 

ON, the output will always be on when the sensor fails; when it is set 
to OFF, the output will always be off when the sensor fails. 

For example, when the unit controls a refrigerator for food, you may 
want to set the TSF to ON if the sensor fails to keep the food cold. 
When it controls a heater, you may want to set the TSF to OFF for 
safety purpose .

Reviews: