background image

         AUBER INSTRUMENTS

  

 

 

 

 

 

 

 

         

WWW.AUBERINS.COM  

 

 

         2015.06                                                                     

   

                                                       P3/5 

 

 
 

Note 6. 

AS, Anti-short Cycle Delay: 

The Anti-short is the delay time to turn on the cooling device. If the cooling 
device is compressor based, compressor should not be turned on immediately 
when it is at high pressure (just after turned off). Otherwise, it may shorten the 
life of compressor. The Anti-Short cycle delay function can be used to prevent 
the rapid cycling of the compressor. It establishes the minimum time that the 
compressor remains off (after reaching cutout) before turns on again. The 
delay overrides any controller demand and does not allow the compressor to 
turn on until the set time-delay value has elapsed. It gives time to release the 
refrigerant pressure through evaporator. It typically set to 4- 6 (minutes). The 
unit is in minutes. This setting is only valid for cooling device control. By 
default, AS is set to 0 (disabled). 
 

Note 7. 

A-M, Power Outage/Startup Mode: 

This parameter determines what the controller should do in an event of power 
interrupt or outage. It also decides how the controller starts the program while 
powered up. A-M can be set to three modes: C, S and M. 
Mode C. After being powered on, the controller will continue the program from 
the where it was powered off.  For example, if step 3 is set for 40 and 5 hours, 
the power was interrupted at 2.1 hours. Then, when the controller power up, 
the controller will continue to control at 40 for 2.9 hr.  
Mode S. The controller will run the program from step 1 every time the 
controller is powered up. This is suitable for situations where the power never 
fails, or when the program mode 

“PrG” 

is 

set to “

off

Mode M. The program will be held at the step at which the controller was 
powered off. The controller will hold the temperature at the set value. The 
controller lower display will flash "hold" and process temperature alternatively. 
This mode is suitable for situations where the operat

or’s

 attention is needed 

after power interruption occurs. 
 

Note 8. 

PrG, Program Mode: 

When PrG is set to “ON”, user can 

program up to 8 steps (Section 7).  When 

set it to “OFF”, this multi

-step function is disabled and controller is in single 

ste

p mode. User can only set “C

-

1” value (without timer t

-1) when disabled. 

Please be aware that if your controller is in single step mode, the green "RUN" 
indicator will be off at all time. The start key, pause key and STEP key are 
disabled. You can check the cooling device indicator (green on the left) and 
heating device indicator (red on the right) for the socket output status. When 
the light is on, the corresponding socket will be activated. 
 

Note 9.

 SFA, Sensor Failure Operation: 

The SFA defines how the output would be if the sensor fails. It can be set to 0-
0, 0-1 or 1-0. Please refer to Table 3 for details. For example, in some 
applications, you may want the cooling device to be working and the heating 
device 

to be off when sensor fails. Hence you need to set SFA to “1

-

0”. 

 

 
Table 3. Output of the controller when sensor fails. 

SFA 

 Controller output when sensor fails 

0-0 

Cooling device off, heating device off 

1-0 

Cooling device on, heating device off 

0-1 

Cooling device off, heating device on 

 

Note 10. 

Time, Time unit setting: 

The Time defines the timer unit setting for its timer function. It can be set to 
hour (H) or minute (M). By default, Time is set to H.  
 

Note 11. 

C-F, Temperature unit: 

ºF: Display in Fahrenheit degree; ºC: Display in Celsius degree.  
 

SET

2 sec

 

68

.

9

ah

^

v

al

^

v

hy

^

v

CDF

^

v

HDF

^

v

ofs

^

v

as

^

v

A-m

^

v

prg

^

v

sfa

^

v

time

^

v

end

SET

SET

 

20

.

0

SET

 

20

.

0

SET

 

1

.

0

SET

  

5

.

0

SET

5

.

0

SET

 

0

SET

M 0

SET

s

SET

  

on

SET

  

0-0

SET

h

Deviation 
high alarm

Deviation low 
alarm

Temp. Control 
Hysteresis Band

Cooling 
Differential

Heating
Differential

Temp. Offset

 Anti-short 
Cycle Delay

Program Modes

Power Outage/
Startup Modes

Sensor Failure 
Operation

Time Unit

^

v

C-F

SET

O

F

Temperature unit

 

Figure 3. Flow chart of setting up parameters. 

 
 
 
 
 

Summary of Contents for TD400P

Page 1: ...Minute Max Programmable Time 799 2 hours or 33 3 days for total 8 steps Audio Alarm High and low limit Sensor Type Silicon Band Gap Sensor Sensor Size 0 25 OD 6 35 mm x 1 25mm long Ambient Temperature 20 50 C 0 120 F Dimension 91 x 140 x 46mm Input Power 85 242 VAC 50 Hz 60 Hz Sensor Cable Length 6 ft 2 m Power Cable Length 3 ft 1 m Warranty One 1 year Either heating or cooling device is limited t...

Page 2: ...erential 0 5 99 9 5 0 4 oFS Ofs Temp Offset 99 9 99 9 0 5 AS AS Anti short Cycle Delay only for cooling socket M 0 M99 0 99 min M 0 6 A M A M Power Outage Startup Modes S M C S 7 PrG PrG Program Modes on off ON 8 SFA SFA Sensor Failure Operation 0 0 0 1 1 0 0 0 9 Time time Time unit H M H 10 C F C F Temperature unit ºF ºC ºF 11 Note 1 AH deviation high alarm AL deviation low alarm Assuming measure...

Page 3: ...ess temperature alternatively This mode is suitable for situations where the operator s attention is needed after power interruption occurs Note 8 PrG Program Mode When PrG is set to ON user can program up to 8 steps Section 7 When set it to OFF this multi step function is disabled and controller is in single step mode User can only set C 1 value without timer t 1 when disabled Please be aware tha...

Page 4: ... part of the program by jumping to a specified program step For example the controller has run 3 minutes in its 2nd step If the user want to skip the rest of the 2nd step and the entire 4th step then the user can jump to step 4 To jump to a specified step 1 Put the controller in either Program Hold or Stop Mode 2 Press STEP key so the controller will flash J PX where J indicates this operation is ...

Page 5: ...ble To install the sensor to the controller 1 Identify the key on the male sensor connector Figure 5 a and the notch on the female connector Figure 5 b 2 Hold the tail of the female connector align the notch and the key and push the female connector forward To remove the connector hold the spring loaded collar on the female connector and pull it back Please see Figure 6 a b c Figure 5 Install the ...

Reviews: