SWA-2451A PID TEMPERATURE CONTROLLER INSTRUCTION MANUAL 

Version 1.0 (Jan, 2019) 

 

 1. Caution

 

 

This  controller  is  intended  to  control  equipment  under  normal  operating 
conditions. If failure or malfunction of the controller may lead to abnormal 
operating  conditions  that  may  result  in  personal  injury  or  damage  to  the 
equipment  or  other  property,  devices  (limit  or  safety  controls)  or  systems 
(alarm  or  supervisory)  intended  to  warn  of  or  protect  against  failure  or 
malfunction of the controller  must be incorporated into and maintained  as 
part of the control system.  

 

Installing  the  rubber  gasket  supplied  will  protect  the  controller  front  panel 
from dust and water splash (IP54 rating). Additional protection is needed for 
higher IP rating.  

 

This controller carries a 90-day limited warranty. This warranty is limited to 
the controller only. 

 

2. Specifications 

Table 1. Specifications 

Input Type 

Thermocouple: K, E, J, T, S. RTD: Pt100, Cu50 

Input Range 

K (-20~2370ºF), S (-20~2912ºF), T (-190~750ºF),  
E (-20~1290ºF), J (-20~1651ºF), Pt100 (-200~1100ºF) 
Cu50 (-56~302) 

Display 

Two lines, four digits. Temperature & time or 
temperature & set temperature. 

Display 
Resolution 

Temperature: 1° C/° F and 0.1° C/ ° F  
Time: 1 second/ minute. 

Accuracy 

Temperature: ±  0.5% of full input range. 
Time: 1 second. 

Control Mode 

Temperature: PID, manual control, on-off,  
Time: timed PID, timed on-off, independent timer 

Timer Mode 

Single delay, double delay, count up, count down 

Timer Range 

1 - 9999 seconds or minutes 

Anti-Short Cycle 
Delay Timer 
Range 

1 - 200 minutes  

Control Output 

SSR control output: 12 VDC, 50 mA 

Alarm 

Timer alarm, process high/low alarm, deviation 
high/low alarm 

Alarm Output 

Relay: 3 A at 240 VAC, 5 A at 120 VAC, or 3 A at 30 
VDC 

Power Supply 

90 ~ 265 VAC, 50 ~ 6 0Hz 

Dimension 

1.89 x 1.89 x 4.25", or 48 x 48 x 108 mm (1/16 DIN) 

Insertion Depth 

From front panel: 3.95" or 100 mm 

Panel Cutout 

1.75 x 1.75" or 44.5 x 44.5 mm 

 

 

 

 

 

3. Terminal Assignment 

TC

1

2

13 14

6

7

8

9

10

5

SSR out

11 12

+

_

input

85-260VAC

3

4

W

R

+

-

R

RTD

COM

(AL1/ AL2)

To  8

AL1

AL2

RST

To  8

 

Figure 1.

 

Wiring diagram 

 

Note: Use a wire or a N.C. switch to jump pin 11 and 12 together to enable the 
timer. 

 

3.1 Sensor Connection 

Please  refer  to  table  3  for  the  input  sensor  type  (Sn)  setting  codes.  The  initial 
setting for input is for a type K thermocouple. Set Sn to the correct sensor code if 
another type of sensor is used. 
 

3.1.1 Thermocouple 

The thermocouple should be connected to terminals 4 and 5. Make sure that the 
polarity  is  correct.  There  are  two  commonly  used  color  codes  for  the  K  type 
thermocouple. US color code uses yellow (positive) and red (negative). Imported 
DIN color code uses red (positive)  and green/blue  (negative). The temperature 
reading will decrease as temperature increases if the connection is reversed. 
 
When  using  ungrounded  thermocouple  that  is  in  touch  with  a  large  conductive 
subject, the electromagnetic field picked up by the sensor tip might be too large 
for the controller to handle, the temperature display will change erratically. In that 
case, connecting the shield of thermocouple to terminal 5 (circuit ground of the 
controller) might solve the problem. Another option is to connect the conductive 
subject to terminal 5.  
 

3.1.2 RTD sensor 

For a three-wire RTD with standard DIN color code, the two red wires should be 
connected  to  the  terminals  4  and  5.  The  white  wire  should  be  connected  to 
terminal 3. For a two-wire RTD, the wires should be connected to terminals 3 and 
4. Jump a wire between terminals 4 and 5. Set controller input type Sn to Pt. 
 

3.2 Power to the Controller 

The power cables should be connected to terminals 6 and 7. Polarity does not 
matter.  It  can  be  powered  by  120V  or  240VAC  power  source.  Neither  a 
transformer nor jumper is needed to wire it up. For the sake of consistency with 
the wiring example described later, we suggest you connect the neutral wire to 
terminal 6 and hot to 7. 
 

3.2.1 Timer reset terminals 

Terminals 11 and 12 are for connecting a reset switch. If you need to start the 
timer  after  controller  is  powered  up,  you  should  short  these  two  terminals 
together with a jumper wire. To use the reset function, these terminals should be 
connected to a switch. Open the contact of the switch will rest the timer. Close 
the contact of the switch will start the timer. Some applications may need a N.O. 

Instruction Manual 

 