When it is set to ON, the output will always be on when the sensor fails; when it 
is set to OFF, the output will always be off when the sensor fails.  
 
For example, when the unit controls a refrigerator for food, you may want to set 
the 

tSF

 to ON if the sensor fails to keep the food cold. When it controls a 

heater, you may want to set the 

tSF

 to OFF for safety purpose. 

 

Note 6.

 

EDT

 is the menu-editing parameter. Select 

tE

 menu for temperature 

control settings; select 

Hu

 menu is for humidity control settings, and select 

SYS

 is for system settings. Note: 

SYS

 menu is only available to TH220-W, 

TH220A, and TH220A-W model.  
 

Note 7.

 

C-F

 is the parameter to set the temperature unit: 

C

 is for Celsius, and 

F

 is for Fahrenheit.  

 

Note 8.

 The parameter 

HdM

 sets the mode for delaying or constraint the 

humidity output. It has three available modes, which are listed and explained in 
the table below.  
 
Table 2. Humidity output delay mode.  

HdM   Mode 

Details 

No delay 

Default value. No delay or constraint on the 
humidity output.   

Time-delay 

Delay the humidity output by a timer set by 

HdT

.  

2 Temperature-

range 

Allow humidity output only when the temperature is 
within a range defined by parameter 

HoS

 and 

HoD

.   

  
 
In situations such as controlling a curing chamber converted from a fridge, 
there is usually a big decrease in the relative humidity (RH%) whenever the 
compressor of the fridge is working. Also, there can be big increase in the 
relative humidity when the user opens the door of the fridge. This kind of 
change in RH% can gradually recover. However, if the controller’s humidity 
control kicks in right away, it creates in a big swing in the RH%.  
 
Using time-delay (

HdM

 = 1) or temperature-range constraint (

HdM

 = 2) can 

help users to reduce the RH% swing.  
 

Note 9.

 The parameter 

HdT

 sets the delay timer for humidity output, it can be 

set from 0 to 999 minutes. When 

HdM

 is set to “1”, the output to the humidity 

control will be delayed for a time period set by 

HdT

.  

 
Please note, the 

HdT

 is effective in both humidifying and dehumidifying mode. 

In dehumidifying mode, the actual delay time of the humidity output is decided 
either by either 

HAS

 or 

HdF

, whichever is longer. 

 

Note 10.

 The parameter 

HoS

 and 

Hob

 set up a temperature range within 

which the humidity output is enabled. 

HoS

 defines a temperature setpoint for 

enabling humidity output, i.e., a lower boundary; and 

Hob

 defines the 

temperature band. Please see the diagram in Figure 6 for how these two 
parameters affect the humidity output.  
 
For example, when HdM = 2, HoS = 36°F, and HoB = 2°F, that means when 
the temperature is below 36°F or above 38°F the humidity output won’t be 
activated even when the controller calls for output to the humidity channel.     

HoS

(HoS + Hob)

Temperature

Time

Humidity output enabled

 

Figure 6. When the humidity output delay mode is 

HdM

 = 2, the humidity 

output is allowed only when the temperature is within the range set by 

HoS

 and 

HoD

 
 
 

Note 11. PSD

 is the Device Access Password (only available to TH220-W and 

TH220A-W model). This parameter is used to lock the access to parameter 
settings on AuberSmart app.  
 

Note 12

RST

 is the reset parameter. Choose “n” to take no action. Chose “y” 

to reset all parameters back to factory settings.   
 
 

6. How to install the sensor to the unit. 

The connector of sensor contains a slot for fitting pin connection. It locates at 
the bottom of the controller. It also has a spring lock to prevent disconnections 
from accidental pulling on the cable.  
 
To install the sensor to the controller: 1) Identify the key on the male sensor 
connector (Figure 7, a) and the notch on the female connector (Figure 7, b). 2) 
Hold the tail of the female connector, align the notch and the key, and push the 
female connector forward.   
 
To remove the connector, hold the spring-loaded collar on the female 
connector and pull it back. Please see Figure 8. 
 

(a) 

 