background image

         AUBER INSTRUMENTS

  

 

 

 

 

 

 

 

         

WWW.AUBERINS.COM  

 

 

         2019-05                                                                     

   

                                                       P3/5 

 

HoS

2

 

HOS 

Humidity Operating 

Setpoint 

-40°F ~ 176°F

 

36 10 

Hob

2

 

HOB 

Humidity Operating 

Band 

0°F ~ 200°F

 

2 10 

System setting (

SYS

)

1

 

PSD

1

 

PSD 

Device Access 

Password 

100 ~ 999 

666  11 

RST

2

 

RST 

Factory Reset 

N, Y 

12 

 

Note 1

: The TH220 model doesn’t have SYS menu and the parameter PSD. Only the 

TH220-W and TH220A-W have the password parameter PSD.  

Note 2

: These parameters, HDM, HDT, HOS, HOD, and RST are only available in 

TH220A and TH220A-W.  

 
 

Details About Each Parameter 

 
Note 1.

 

tSP

 and 

HSP

 are the setpoints for temperature-control and humidity-

control respectively. 

tdF

 and 

HdF

 are the control-differential (i.e., control 

hysteresis band) to prevent the load being turned on and off frequently. These 
hysteresis bands are one-sided. 

tCM

 is the temperature control mode, which 

can be set to heating (

HT

) or cooling (

CL

). 

HCM

 is humidity control mode, 

which can be set to humidifying (

H

) or dehumidifying (

dEH

).  

 
In the heating mode of the temperature-control channel, the controller will 
energize the output socket till the temperature rise to the setpoint 

tSP

; the 

output socket will be energized again when the temperature drops below (

tSP

 - 

tDF

). In contrast, in the cooling mode of the temperature-control channel, the 

controller will energize the output socket till the temperature drops to the 
setpoint 

tSP

; the output socket will be energized again when the temperature 

rises above (

tSP

 + 

tDF

). Please refer to the Figure 4 below when the output 

relay will be turned on.      
 

(TSP + TDF)

TSP

Temperature

Time

Cooling Mode

Relay ON

(TSP – TDF)

TSP

Temperature

Time

Relay ON

Heating Mode

 

Figure 4. Temperature output is decided by 

tSP

 and 

tDF

 
 
Similarly, in the humidifying mode of the humidity-control channel, the 
controller will energize the output socket till the temperature rise to the setpoint 

HSP

; the output socket will be energized again when the temperature drops 

below (

HSP

 - 

HDF

). In contrast, in the dehumidifying mode of the humidity-

control channel, the controller will energize the output socket till the humidity 
drops to the setpoint 

HSP

; the output socket will be energized again when the 

humidity rises above (

HSP

 + 

HDF

). Please refer to the Figure 5 below when 

the output relay will be turned on.      

(HSP + HDF)

(HSP – HDF)

HSP

Humidity

Time

Relay ON

Humidifying 

Mode

HSP

Humidity

Time

Dehumidifying 

Mode

Relay ON

       

Figure 5. Humidity output is decided by 

HSP

 and H

DF

 
 
Small differential gives tight control. Large differential reduces the frequency of 
cycle on and off, and it will extend the life of relay and compressor. 

 

Note 2.

 

toF

 and 

HoF

 are the sensor calibration offset for temperature and 

humidity readings respectively. The offset is used to set an input offset to 
compensate the error produced by the sensor or input signal itself. 
 
For example, for temperature reading, if the unit displays 37ºF when the actual 
temperature is 32ºF, setting parameter 

toF

 = - 5 will make the controller display 

32ºF. 
 

Note 3.

   The low limit alarm should be always lower than the high limit alarm. 

When the measured temperature is higher than 

tAH

, the temperature high limit 

alarm will be on; when the measured temperature is lower than 

tAL

, the 

temperature low limit alarm will be on. 
 
Similarly, for humidity readings, when the measured humidity is higher than 

HAH

, the humidity high limit alarm will be on; when the measured humidity is 

lower than 

HAL

, the humidity low limit alarm will be on. 

 
When an alarm is on, the display will be flashing between the measured value 
and the alarm type. To mute the alarm, press the DOWN key momentarily. 
When the alarm is muted, the alarm indicator (see Figure 1, the small dot on 
the last digit) will be lit. If the measured value gets out of the alarm zone then 
gets back to the alarm zone again, the alarm will be on again. To resume the 
alarm, press the UP key, the alarm indicator should turn off.  
 
To disable the alarm, set High Limit Alarm = Low Limit Alarm.  For example, 
you can set both 

tAH

 and 

tAL

 to 32°F, so the temperature alarm will be 

disabled.  
 

Note 4.

 The parameter 

tAS

 and 

HAS

 are Anti-Short Cycle Delay for cooling 

and dehumidifying respectively. The controller is used for cooling or 
dehumidifying control, and the load is a compressor, use the parameter 

tAS

 or 

HAS

 to prevent the compressor being turned on again when it is at high 

pressure (i.e., just after it is turned off). Otherwise, it may shorten the life of 
compressor. The Anti-Short Cycle Delay function is used to prevent the rapid 
cycling of the compressor. It establishes the minimum time that the output 
contact remains open (after reaching cutout) before closing again. The delay 
overrides any load demand and does not allow the output contact to close until 
the set time-delay value has elapsed. It gives time to release the refrigerant 
pressure through evaporator. It is typically set to 4 - 6 minutes.  
 

Note 5.

 Parameter 

tSF

 and 

HSF

 are the Sensor Failure Operation for 

temperature and humidity control respective, they can be set to ON or OFF. 