The user should decide the appropriate configuration for each output socket 
based on the user’s particular application. Please refer to section 4.5 and 
second 5 for details.  
 

4.4 Change the Setpoints 

The setpoint for temperature is 

TSP

 (

TSP

) and the setpoint for humidity is 

HSP

 (

HSP

). To access the setpoints, simply short-press the SET key, and 

then the top window will show 

TSP

 and the bottom window will show its value. 

Use UP or DOWN arrow keys to adjust the value, and short-press the SET key 
again to save the new value and go to the 

HSP

 setting. The way to adjust and 

save the setting is the same as for temperature setpoint. Once you press the 
SET key again, the controller will return to its normal operation mode. Please 
see Figure 2 for how to access the setpoints.   
 

SET

Temp

 50

.

5

 72

.

0

RH

Temp

 75

.

0

TSP

RH

Temp

 40

.

0

HSP

RH

Short-press

Short-press

Short-press

Normal 

Operating 

Mode

Temperature 

Setpoint

Humidity 

Setpoint

SET

SET

 

Figure 2. How to access setpoints. 

 
  

4.5 Adjust Parameters 

Other control parameters are grouped into three sub-menus: temperature 
(

tE

), humidity (

Hu

), and system (

SYS

)*. To access these parameters, long-

press SET key for 3 seconds, the top window will show 

EDT

 (

EDT

). Then use 

UP or DOWN arrow key to select the sub-menu item (

tE

Hu

, or 

SYS

) in the 

bottom window, then press SET key again to confirm the selection. Please see 
Figure 3 for how to access these parameters. The details for each parameter 
are explained in section 5.  
 

Temp

 50

.

5

 72

.

0

RH

Temp

TE

EDT

RH

Temp

SYS

EDT

RH

Temp

HU

EDT

RH

Temp

 50

.

5

 72

.

0

RH

SET

Long-press 

3 seconds

SET

short-press 

to confirm

SET

short-press 

to confirm

SET

short-press 

to confirm

Go through all parameters in 

system menu

Go through all parameters in 

temperature menu

Go through all parameters in 

humidity menu

Normal Operating Mode

Normal Operating Mode

 

 

Figure 3. How to access parameter menus.  

 
  

5.

 

Parameter Settings 

All parameters are listed in Table 1. When a parameter is displayed in the top 
window, its value is displayed in the bottom window. The user can use the UP 
or DOWN arrow key to adjust the value in the bottom window, then press the 
SEK key to save the new value and go to the next parameter. If no key is 
pressed for 10 seconds, the controller will exit to its normal operating mode.  
 

 

Table 1. Parameters.  

Code

 

Description Setting 

Range 

Initi

al 

No

te 

Short-press SET Key 

tSP 

tSP

Temp. Setpoint 

-40ºF ~ 176ºF 

-40ºC ~ 80ºC 

75.0  1 

HSP 

HSP

Humidity Setpoint 

0 ~ 99.9% RH 

40.0  1 

Long-press SEK Key 

Edt 

EDT

Edit parameters 

tE

: temperature menu  

Hu

: humidity menu 

SYS

*: system menu 

tE 6 

Temp. control settings (

tE

C-F 

C-F

Temp. Unit 

C

: Celsius 

F

: Fahrenheit 

F 7 

tCM 

tCM

Temp. Control Mode 

Ht

: heating mode 

CL

: cooling mode 

CL 1 

tdF 

TDF

Temp. Control 

Differential 

0 ~ 50.0 

3.0 

toF 

toF

Temp. Calibration 

Offset 

-10.0 ~ 10.0 

tAH 

TAH

Temp. High  

Limit Alarm 

-40ºF ~ 176ºF 

-40ºC ~ 80ºC 

95.0 

tAL 

TAL

Temp. Low  
Limit Alarm 

-40°F ~ 176ºF 

-40°C ~ 80ºC 

32.0 

tAS 

TAS

Temp. Anti-short 

Cycle Delay (only for 

cooling) 

0 ~ 12 min 

tSF 

TSF

Temp. Sensor 

Failure Operation 

ON

: output energized 

OFF

: output de-

energized 

OFF  5 

Humidity control settings (

Hu

HCM 

HCM

Humidity Control 

Mode 

deH

: dehumidifying 

H

: humidifying 

H 1 

HdF 

HDF

Humidity Control 

Differential 

0% ~ 50.0% 

3.0

HoF 

HoF

Humidity Calibration 

Offset 

-10.0% ~ 10.0% 

0% 

HAH 

HAH

Humidity High Limit 

Alarm 

0% ~ 99.9% 

90.0

HAL 

HAL

Humidity Low Limit 

Alarm 

0% ~ 99.9% 

10.0

HAS 

HAS

Humidity Anti-short 

Cycle Delay (only for 

dehumidifying) 

0 ~ 12 min 

HSF 

HSF

Humidity Sensor 

Failure  

Operation 

ON

: output energized 

OFF

: output de-

energized 

OFF  5 

HdM

2

 

HDM

Humidity Output 

Delay Mode 

0, 1, 2

 

0 8 

HdT

2

 

hdt

Humidity Delay 

Timer 

0 ~ 999 min

 

5 9 