background image

TH146-N-U

User’s Guide

Non-programmable H/C Controller

TH146-N-U 

                                              9/12

Press the 

Mode

 button to place the system in one of the following

modes:

Press the 

 button to select the fan operating mode.

In automatic mode, the fan runs only when heating or cooling is
activated. 

NOTE

: For gas-operated HVAC systems, there might

be a delay before the fan starts or stops when heating is acti-
vated or deactivated.

In continuous mode, the fan runs continuously and the   sym-
bol is displayed. 

NOTE

: If Smart Fan is enabled, when the ther-

mostat is in unoccupied mode, the fan runs only when heating
or cooling is activated.

The controller can display either the indoor humidity level or the out-
door temperature (see page 8, item 14).

The actual (measured) indoor temperature is normally displayed. To
view the setpoint temperature, press one of the 

 buttons once.

The setpoint is displayed for 5 seconds and is indicated by the 
symbol. 

To modify the temperature setpoint, press one of the 

 buttons

until the desired temperature is displayed.

NOTE

: If the controller is in automatic heat/cool changeover (see

section 5.1), the setpoint is automatically reduced or raised by 1°C
(1.8°F) when the controller switches to heating mode or to cooling
mode respectively. For example, if the setpoint is 24°C (75°F) in
heating mode, it will become 25°C (77°F) in cooling mode and will
return to 24°C (75°F) when the controller switches back to heating
mode.

NOTE

: Skip this section if you do not have a humidifier connected to

the controller. 

The humidity level can be set manually or automatically (see
page 8, item 16).

System fault 
indicator

Temperature adjustment

Fan operating 
mode selection

System operating 
mode selection

System operating mode

Fan is in 
continuous mode

Unoccupied 
mode is On

Outdoor temperature 
or indoor humidity

Indoor temperature

Auxiliary heat is On

Heating is On

Cooling is On

Emergency heat 
indicator

Dual energy

Humidifier 
is On

Appears when the 
temperature setpoint 
is displayed

5. Operation

5.1

 System Operating Mode

HEAT

The system is in heating mode.

COOL

The system is in cooling mode.

AUTO

The system is in automatic changeover mode. (The 
system switches between heating mode and cooling 
mode to maintain the desired temperature.)

OFF

The system is off.

EHEAT

The system is in emergency heat mode. Only auxiliary 
heating is used when there is a call for heat. (This 
mode applies only when the controller is connected to 
a heat pump equipped with auxiliary heating).

5.2

 Fan Operating Mode

5.3

 Indoor Humidity / Outdoor Temperature Display

5.4

 Temperature Setting

5.5

 Humidity Setting

Outdoor

temperature

Indoor 
humidity

Summary of Contents for TH146-N-U

Page 1: ...e module Install the control module near the heating cooling system away from any heat source Install the console in a central location Avoid locations with air drafts e g top of staircase or air outlet or stagnant air behind a door Do not install the console on a wall hiding air ducts nor expose it to direct sunlight NOTE If this controller replaces an old thermostat any two of the wires that wer...

Page 2: ...on the side of the plenum and position it such that its aperture faces the air flow Connect the sensor to controller terminals PS and CS no polarity For more information refer to the instructions provided with the sensor NOTE The maximum wiring length is 30 m 100 ft NOTE The dual energy input can be used only with a heat pump equipped with auxiliary heat The dual energy input can be connected to t...

Page 3: ...here is not already a furnace the auxiliary heat source is installed at the same time as the heat pump In this type of installation the indoor coils are located upstream of the auxiliary heat When the controller is configured for a new installation the heat pump and the auxiliary heat can operate simultaneously Interstage Delay is the time allocated for the temperature to return to an acceptable v...

Page 4: ...A W1 Auxiliary heat 1 24 Vac 1 A W2 Auxiliary heat 2 24 Vac 1 A W3 O B Reversing valve 24 Vac 1 A G Fan 24 Vac 1A L Fault 24 Vac 5 mA WW Defrost 24 Vac 5 mA NC Not used HVAC Terminal Device 1H 2H 3H 1C 2C 3C 1H1C 1H2C 2H1C 2H2C 2H3C 3H1C 3H2C 3H3C TH Console Connect the console sensor between the TH terminals no polarity TH PS Plenum sensor Connect the plenum sensor between the PS and CS terminals...

Page 5: ...TH146 N U 5 12 Wiring Diagram 2H1C Heat Pump New Installation AC146 410 AC144 03 CT241 Humidifier Dehumidifier Compressor Auxiliary Heat Reversing Valve Fan Fault Defrost Dual Energy ...

Page 6: ...TH146 N U 6 12 Wiring Diagram 3H2C Heat Pump Add on Installation AC146 410 AC144 03 CT241 Fault Defrost Reversing Valve Compressor 1 Compressor 2 Furnace Fan Limit Humidifier Dehumidifier Dual Energy ...

Page 7: ...TH146 N U 7 12 Wiring Diagram 3H2C HVAC AC146 410 AC144 03 CT241 Cooling Unit 1 Cooling Unit 2 Heating Unit 1 Heating Unit 2 Fan Heating Unit 3 Humidifier Dehumidifier ...

Page 8: ...ses above the Fan Limit see item 11 and stops when the tem perature drops 12 C below the Fan Limit Note The fan will not start if the plenum temperature sensor is not connected to the controller 11 Fan limit 38 to 90 C 100 to 194 F 80 C 176 F This parameter is available only when gas heating is selected see item 10 WARNING FLMT can be used in parallel with an UL353 approved device but they do not ...

Page 9: ...or to cooling mode respectively For example if the setpoint is 24 C 75 F in heating mode it will become 25 C 77 F in cooling mode and will return to 24 C 75 F when the controller switches back to heating mode NOTE Skip this section if you do not have a humidifier connected to the controller The humidity level can be set manually or automatically see page 8 item 16 System fault indicator Temperatur...

Page 10: ...ture 20 C to 50 C 4 F to 122 F Humidity conditions 0 to 95 non condensing Dimensions 79 x 79 x 24 mm 3 1 x 3 1 x 1 in Honeywell warrants this product excluding battery to be free from defects in the workmanship or materials under normal use and service for a period of three 3 years from the date of purchase by the consumer If at any time during the warranty period the product is determined to be d...

Page 11: ...TH146 N U 11 12 ...

Page 12: ...TH146 N U 12 12 Printed in USA 09 2011 ...

Reviews: