background image

 

 

 

  

WARNING 

POSSIBLE INJURY OR DEATH 

Should the gas supply fail to shut off or if overheating occurs, shut off 
the gas valve to the furnace before shutting off the electrical supply.”

 

 

SERVICING 

 

  

WARNING 

POSSIBLE INJURY OR DEATH 

Your furnace should be inspected by a qualified service agency yearly 
before  turning  the  furnace  on.  Particular  attention  should  be  given  to 
the following items. 

 

 WARNING 

CARBON MONOXIDE POISONING 

 

Doors must be properly sealed and vent cap assembly must 
be installed correctly and sealed were needed. 

 

Combustion  air  must  NOT  be  drawn  from  within  any  living 
area. 

 

DO  NOT  vent  exhaust  into  living  area  or  outside  into  an 
enclosed porch area. 

 

DO  NOT  vent  any  other  appliance  with  venting  systems 
serving the furnace. 

 

DO NOT allow snow or any objects to block  exhaust system 
or combustion air to the furnace. 

 

1. 

Inspect  furnace  installation  and  vent  termination  to  be  sure 
furnace  is  properly  secured  in  place,  that  vent  terminates  to  the 
atmosphere, and that vent tubes overlap properly and vent is tight 
against  outer  door.  (See  installation  manual  supplied  with 
furnace).  All  exhaust  system  tubes  must  overlap  no  less  than  1-
1/4”.  All  air  intake  tubes  must  overlap  no  less  than  1/2”  and  be 
positioned for proper function. 

2. 

Inspect  chamber  and  venting  to  assure  that  these  components 
are  physically  sound,  without  holes  or  excessive  corrosion  and 
that  the  installation  and/or  reinstallation  are  in  accordance  with 
Atwood  Mobile

 

Products  Installation  Instructions.  (Reference 

Installation Manual supplied with furnace.) 

3. 

Check  the  base  on  which  furnace  is  mounted.  Be  sure  it  is 
physically sound, void of any sagging, deterioration, etc. 

4. 

Inspect furnace, the venting, ducting and the gas piping to furnace 
for  obvious  signs  of  deterioration.  Correct  any  defects  at  once. 
Always verify proper operation of furnace after servicing. 

5. 

Do  not  allow  flue  gas  exhaust  to  have  extended  contact  with 
exterior sidewall of recreation vehicle. It will cause the material to 
degrade over time. 

6. 

You,  as  the  owner/user,  should  inspect  the  furnace  monthly 
during the heating season for presence of soot on vent. Operating 
the  furnace  under  this  condition  could  lead  to  serious  property 
damage, personal injury or loss of life. If soot is observed on the 
vent,  immediately  shut  furnace  down  and  contact  a  qualified 
service agency. 
 

 WARNING 

FIRE OR EXPLOSION

 

 

Use the correct gas specified for your furnace. 

 

Only  a  qualified  Service  Technician  may convert  an  AFLAC 
series furnace from LP to NAT or NAT to LP 

 

GAS CONVERSION 

 
All models, except the AFLAC series, are designed for LP GAS ONLY 
and  cannot  be  converted  to  natural  gas.  To  verify  the  setting  of  your 
furnace, open furnace door and check the model number on the labels, 
(see table below). Use only the type of gas your furnace has been set 
for. 
 

Model 

Gas Type 

All - AFSA 

LP ONLY 

All 

– AFS  

LP ONLY 

All 

– AFM 

LP ONLY 

All 

– AFLD 

LP ONLY 

All 

– AFLA 

LP or NATURAL 

 

 

AC model units come equipped with a convertible gas control. 

 

Each  unit  is  supplied  with  two  main  burner  orifices.  One  will  be 
installed the other will be attached to the valve. 

 

Each  orifice  will  be  clearly  marked  with  a  drill  size  as  shown 
below. 

 

The  pressure  settings  of  the  convertible  valve  are  set  based  on 
the orifice being used pressure can be check based on the rating 
plate information or table below. Valves are not adjustable.

 

 

Use Loctite #RC609 or some other thread lock sealant on orifice 
threads when installing a new orifice.

 

 

A 1/8” NPT plug is provided in the valve to make a connection to 
check gas pressure. 

 

 
GAS TYPE 

BTU/HR 

LINE 
PRESSURE 

REG. 
PLUG 
SETTING 

DRILL 
SIZE 

Propane 
(LP) 

35,000 

11” W.C. 

10.2

” W.C. 

#51 

Propane 
(LP) 

40,000 

11” W.C. 

10.0” W.C. 

#49 

Natural 
(NAT) 

35,000 

7” W.C. 

4.

0” W.C. 

3.0mm 

Natural 
(NAT) 

40,000 

7” W.C. 

3.5” W.C. 

#30 

W.C.= water column 
 
VALVE CONVERSION 

 

 
 
ANNUAL PREVENTATIVE MAINTENANCE INSPECTION 

 
A  qualified  RV  service  technician  should  perform  the  following 
preventative maintenance and safety checks ANNUALLY. 
Failure to properly maintain the furnace may void the furnace warranty 
and can result in unsafe furnace operation. 
Preventative maintenance not covered under warranty. 
 

 

AIR WHEEL:

 Clean and clear any obstructions. Operating 

furnace with any obstructing in the blower will damage wheel 
making replacement necessary and cause over heating cycling. 

 
1. 

See drawing to check which plug to use marking is on side of 
adjustment reg. plugs. Furnace come with LP plug installed and 
the natural plug in the bag with the natural gas orifice. NAT or LP 
is stamped on the side. The type of gas being used must match 
the plug and orifice in use when installed. 

2. 

Unscrew plug and remove from valve reg. tower. DO NOT 
remove rod from inside the reg. tower or make any adjustments. 

3. 

A.   When set for LP and NAT is required: 

Unscrew plug and replace the correct plug into tower for 
NAT. 
NAT should now be visible. 
Finger tighten plug or with small wrench. DON’T over 
tighten. 

Reviews: