Troubleshooting
TROUBLESHOOTING GUIDE
PROBLEM
CAUSE
CORRECTION
U.V. lamp will not light Check input voltage if below
Install a voltage regulator
or
above
120
volts
Electrical cord disconnected
Check, replace
or
outlet
defective
Defective
U.V.
lamp Replace
lamp
Defective
lamp
ballast Check
output
voltage
Replace
ballast
Loose
open-circuit
wire
Trace
out
and
repair
Leak at quartz nipple
Defective or cracked O-Ring
Replace O-Ring
O-Ring not seated properly
Replace O-Ring
Cracked
quartz
sleeve Replace
quartz
sleeve