CONDENSINOX -
Installation, Use and Maintenance
Line
No.
Programming
Access
Adjustment range
Default value
Customer
setting
5061
Electric resistance release
S
24h/24 | DHW release | timer
prog. 4/DHW
DHW release
5062
Elec. resistance regul.
S
external thermostat | DHW
sensor
DHW sensor
5085
Excess heat evacuation
S
stop | start
on
5090
With storage tank
S
yes | no
no
5092
With prim contr/primary pump
S
yes | no
no
5093
With solar integration
S
yes | no
yes
5101
Min. pump rot. speed
S
0 … 100%
40%
5102
Max. pump rot. speed
S
0 … 100%
100%
Confi guration
5710
Heating circuit 1
M
stop | start
stop
5711
Cooling circuit 1
M
none | 4-tube cooling system
none
5715
Heating circuit 2
M
stop | start
stop
5721
Heating circuit 3
M
stop | start
stop
5730
DHW sensor
M
sensor | thermostat | DHW outlet
sensor B38
sensor
5731
DHW pump/valve
M
no fill request | filling pump |
distribution valve
filling pump
5732
Stop DHW pump reverse valve
M
0 … 10 s
0 s
5733
DHW pump stop freq.
M
0 … 10 s
0 s
5734
DHW direct valve base pos.
S
last request | heating circuit |
DHW
last request
5736
Separate DHW circuit
M
stop | start
stop
5737
DHW dist. valve action dir.
S
DHW ON position | heating circuit
ON position
DHW ON position
5738
Dist. valve median pos. DHW
S
stop | start
stop
5774
Heat pump ctrl+DHW dir.valve
M
all requests | only HC1/DHW
requests
all requests
5840
Solar adjustment component
M
filling pump | distribution valve
filling pump
5841
External solar exchanger
M
common | DHW tank | storage
tank
common
5870
Combi DHW tank
M
yes | no
no
5890
Relay QX1 output
M
none | consum. circuit 1 pump
Q15 | boiler pump Q1 | alarm
output K10 | HC3 pump Q20 |
consum. circuit 2 pump Q18 |
cascade pump Q25 | HC1 pump
Q2 | HC2 pump Q6 | DHW pump/
valve Q3 | status message K36
alarm output K10
5891
Relay QX2 output
M
As line 5890
none
5892
Relay QX3 output
M
As line 5890
boiler pump Q1
5931
Sensor input BX2
M
none | common
fl
ow sensor B10 |
common return sensor B70
none
5932
Sensor input BX3
M
As line 5931
none