Page 102 / 116
00CNO0183-C
CONDENSINOX -
Installation, Use and Maintenance
Line
No.
Programming
Access
Adjustment range
Default value
Customer
setting
Heating Circuit 3
1310
Comfort setpoint
U
4 … 35°C
20°C
1312
Low setpoint
U
4 … 35°C
18°C
1314
Frost protection setpoint
U
4 … 35°C
10°C
1316
Maximum comfort setpoint
S
4 … 35°C
35°C
1320
Curve slope
U
0.10 … 4.00
1.5
1321
Curve offset
S
-4.5 … 4.5 °C
0°C
1326
Curve adaptation
S
stop | start
stop
1330
Summer/winter heating limit
U
8 … 30°C
19°C
1332
Daily heating limit
S
-10 … 10°C
-3°C
1340
Min start temperature setpoint
M
8 … 95°C
8°C
1341
Max start temperature setpoint
M
8 … 95°C
80°C
1342
Room thermostat start temp. setpoint
S
8 … 95°C
65°C
1346
Heating request frequency
M
0 ... 600 s
0 s
1350
Room influence
S
1 … 100%
20%
1360
Room influence limitation
S
0.5 … 4°C
1°C
1370
Fast reheating
S
0 … 20°C
3°C
1380
Fast lowering
S
stop | until low setpoint | until
anti-frost setpoint
stop
1390
Max. optimisation on start-up
S
00:00 … 06:00
00:00
1391
Max. optimisation on cut-out
S
00:00 … 06:00
00:00
1400
Start increase reduction
S
-30 … 10°C
-5°C
1401
End increase reduction
S
-30 … 10°C
-15°C
1409
Uninterrupted pump operation
S
yes | no
no
1420
HCP overheating protection
S
stop | start
on
1430
Raising of mixing valve
S
0 … 50°C
3°C
1432
Type of servomotor
S
all or nothing | 3-position
3-position
1433
Differential
S
0 … 20°C
2°C
1434
Servomotor travel time
S
30 … 873 s
120 s
1450
Controlled drying function
M
None | Functional heating |
Heating ready for occup. |
Functional/ready heating |
Ready/functional heating |
Manual
None
1451
Manual drying setpoint
M
0 … 95°C
25°C
1455
Floor drying current setpoint
U
0 … 95°C
0°C
1456
Current drying day
U
0 … 32
0
1461
Excess heat evacuation
S
stop | heating mode | permanent
permanent
1470
With storage tank
S
yes | no
no
1472
With prim contr/primary pump
S
yes | no
no
1480
Pump speed reduction
S
temperature level | characteristic
characteristic
1482
Min. pump rot. speed
S
0 … 100%
50%
1483
Max. pump rot. speed
S
0 … 100%
100%
1488
Curve cor. at 50% rot. speed
S
0 … 100%
33%
1489
Speed adj. filtr. const. time
S
0 … 20 min
5 min
1490
Corr. rot. speed adj. t° setpoint
S
yes | no
yes
1498
Temp. level switching
S
frost protection | low | comfort
low
1500
Operating mode changeover
S
none | protection mode | low |
comfort | automatic
protection mode