Line
Function
Setting range or display
Setting increment
Basic setting
Time program 5 / Cooling
(Not available with DHW model).
Holidays, circuit 1
641
U
Pre-selection of the holiday period
Period 1 to 8
Period 1
642
U
Date of start of holidays (day/month).
01:01... 31.12
1
643
U
Date of end of holidays (day/month).
01:01... 31.12
1
648
U
Operating level (during the holidays)
Frost protection, reduced
Frost
protection
Holidays, circuit 2
If the installation is composed of 2 heating circuits (only displayed with 2nd circuit kit option)
651
U
Pre-selection of the holiday period
Period 1 to 8
Period 1
652
U
Date of start of holidays (day/month).
01:01... 31.12
1
653
U
Date of end of holidays (day/month).
01:01... 31.12
1
658
U
Operating level (during the holidays)
Frost protection, reduced
Frost
protection
Setting the heating, circuit 1
710
U
Ambient comfort temperature value
Reduced temperature …
max. comfort reference value .
0.5 °C
20 °C
712
U
Reduced setpoint
frost protection temperature …
comfort temperature
0.5 °C
18 °C
714
U
Ambient "antifreeze" temperature value
4 °C… reduced temperature
0.5 °C
8 °C
716
S
Maximum comfort value
20 °C... 35 °C
1 °C
28 °C
720
I
slope of the heating curve (see
0 1 4
0 02
0.5
721
I
Translation of the heating curve
-4.5 °C... 4.5 °C
0.5 °C
0
726
I
Translation of the heating curve
Stop| Start
Stop
Warning!
Do not modify, leave on Stop.
730
I
Summer/winter heating limit
8 °C... 30 °C
0.5 °C
18 °C
When the mean of the external temperatures over the last 24 hours reaches 18°C the regulator stops the heating (economy).
In summer operation, the display shows "Eco". This function is only active in automatic operation.
732
S
Daily heating limit
-10 °C... 10 °C
1 °C
-3 °C
This function permits, between seasons, to deviate partially from the automatic switching between summer/winter.
If the value is increased, the switch to summer operation is delayed.
If the value is reduced, the switch to summer operation is brought forward.
This function is only active in automatic operation.
740
S
min. initial reference value . (for fan-
convector)
8... 95 °C
1 °C
8 °C
741
S
Max. start value
8... 95 °C
1 °C
80 °C
Heated floor= 50 °C
Important remark
:
The maximum limit is not a safety function as that required for under-floor heating.
750
S
Influence of the ambient temperature
1%... 100%
1%
20%
If the installation is equipped with an ambient sensor:
This function allows the influence of the ambient temperature on the regulation to be chosen.
If no value is entered, the regulation is via the water logic.
If the parameter is set to 100%, the regulation is only made using the ambient temperature.
790
S
Maximum optimisation when started
0 360 min
10 min
120 min
(anticipation of start to reach the comfort reference value).
Installation and operating manual
"
1605 - EN
"
alfea hybrid duo heat pump oil low NOx CH
- 42 -