Line
Function
Setting range or display
Setting increment
Basic setting
44
I
Operation HC2 (command HC2)
Common to CC1, independent
Common
with heating
circuit 1
Common to CC1 or independent This function permits the choice to be made if the ambient sensor (in option) has an
action on the two zones or on a single zone.
46
I
CCP operation (command of sanitary circuit circulator, output QX2)
Common to CC1 or independent (Not concerned)
Common
with heating
circuit 1
70
S
Software version of the display
Timer programme for heating, circuit 1
500
U
Pre-selection (day / week)
Mon-Sun Monn-Fri Sat-Sun
Monday Tuesday…
Mon-Sun
501
U
1st phase (in service)
00:00... --:--
10 min
06:00
502
U
1st phase (not in service)
00:00... --:--
10 min
22:00
503
U
2nd phase (in service)
00:00... --:--
10 min
--:--
504
U
2nd phase (not in service)
00:00... --:--
10 min
--:--
505
U
3rd phase (in service)
00:00... --:--
10 min
--:--
506
U
3rd phase (not in service)
00:00... --:--
10 min
--:--
516
U
Retrieval of the standard settings
No, Yes
No
Yes + OK: The standard values, saved in the regulator, replace and cancel the personalised heating programmes.
Your personal settings are therefore lost.
Timer programme for heating, circuit 2
If the installation is composed of 2 heating circuits (only displayed with 2nd circuit kit option)
520
U
Pre-selection (day / week)
Mon-Sun Monn-Fri Sat-Sun
Monday Tuesday…
Mon-Sun
521
U
1st phase (in service)
00:00... --:--
10 min
06:00
522
U
1st phase (not in service)
00:00... --:--
10 min
22:00
523
U
2nd phase (in service)
00:00... --:--
10 min
--:--
524
U
2nd phase (not in service)
00:00... --:--
10 min
--:--
525
U
3rd phase (in service)
00:00... --:--
10 min
--:--
526
U
3rd phase (not in service)
00:00... --:--
10 min
--:--
536
U
Retrieval of the standard settings
No, Yes
No
Yes + OK: The standard values, saved in the regulator, replace and cancel the personalised heating programmes.
Your personal settings are therefore lost.
Heating time program 4 / DHW
560
U
Pre-selection (day / week)
Mon-Sun Monn-Fri Sat-Sun
Monday Tuesday…
Mon-Sun
561
U
1st phase (in service)
00:00... --:--
10 min
00:00
562
U
1st phase (not in service)
00:00... --:--
10 min
05:00
563
U
2nd phase (in service)
00:00... --:--
10 min
15:00
564
U
2nd phase (not in service)
00:00... --:--
10 min
18:00
565
U
3rd phase (in service)
00:00... --:--
10 min
--:--
566
U
3rd phase (not in service)
00:00... --:--
10 min
--:--
576
U
Retrieval of the standard settings
No, Yes
No
Yes + OK: The standard values, saved in the regulator, replace and cancel the personalised heating programmes.
Your personal settings are therefore lost.
Installation and operating manual
"
1605 - EN
"
- 41 -