Manual, Control Module, PROFINET, DL12
Document #9620-20-C-DL12-06
Pinnacle Park • 1031 Goodworth Drive • Apex, NC 27539 • Tel: 919.772.0115 • Fax: 919.772.8259 •
C-41
8. Loosen the (2) M3 pan head captive screws and remove LED window.
9. Locate reset button between BF and E2 LED.
10. Use a non‑conductive tool (e.g. plastic stylus) to press on the reset button ‑> the SF
LED will change from GREEN to blinking RED, indicating that the module will
clear its name and IP address after the next power cycle.
Figure 6.3—Reset Button
Bus Failure (BF) LED
Ethernet (E1) LED
Master Side Ethernet Port
Ethernet (E2) LED
Tool Side Ethernet Port
System Failure (SF) LED
Reset Button
(Reset to Factory Settings)
(2) M3 Captive Head Screw
Window
11. Re‑install the window and tighten the M3 pan head captive screws.
12. Disconnect the 5‑pin power cable to the connectors on the module.
13. Connect the M12 cable and the 5‑pin power cable to the connectors on the module.
14. The new module may be found using the default PROFINET station name and
configured to the appropriate station name for your application, or the network
controller may be configured to automatically rename the module when it detects
the default name.
15.
Within a few seconds after configuring, it should be operating on the network.
16. The SF and BF LED should be GREEN when the network is operating without
errors.
17. After repair is complete, return all circuits to normal operation (e.g. electrical, air,
water, etc.).