Manual, Control Module, PROFINET, DL12
Document #9620-20-C-DL12-06
Pinnacle Park • 1031 Goodworth Drive • Apex, NC 27539 • Tel: 919.772.0115 • Fax: 919.772.8259 •
C-39
Table 6.1—Troubleshooting
Symptom
Possible Cause
Correction
No power on the
Tool side.
Latch command not
issued.
Verify that the Latch command has been issued.
Tool Power is On bit.
Verify that the
Tool Power is On
bit is
HIGH
.
Tool Present bit.
Verify that the
Tool Present
bit
is
HIGH
.
Loss of auxiliary
power on the
Tool side.
US1 power loss.
Loss of US1 (Logic) power on the Master side will cause loss of US2
(Auxiliary) power to the Tool. The Arc Prevention Circuit relies on US1 power to
operate. Restore US1 power to the Master to restore US2 power to the Tool.
6.2 Service Procedures
Inspection, adjustment, and replacement procedures are covered in the following section.
6.2.1 Seal Replacement
Parts required: Refer to
The seal protects the electrical connection between the Master and Tool module. If the seal
becomes worn or damaged, it must be replaced.
1. Place the Tool in a secure location.
2. Uncouple the Master and Tool plates.
3. Turn off and de‑energize all energized circuits (e.g. electrical, air, water, etc.).
4.
To remove the existing seal, pinch the edge of the seal with your fingers and pull the seal away
from the pin block on the Master.
5. To install a new seal, stretch the new seal over the shoulder of the pin block.
6.
Push the seal hub down against the pin block using your finger tip.
7. After the procedure is complete, resume normal operation.
Figure 6.1—V-ring Seal Replacement
V-ring Seal
Stretch seal over shoulder of pin block
and push seal hub down against
the pin block with finger tip
V-ring Seal
Pinch edge of seal with
fingers and gently pull
away from pin block