www.atestgaz.pl
Passive
- see the connection below:
Figure 5: A passive output
In that mode the circuit of a current loop is supplied from an external source of power voltage (24...36 V).
Levels of the output current:
Status of operation
Output current
The system is stopped (STOP mode)
DEF
Detector is missing (no detector is connected)
3mA
Detector inhibited
DEF
Detector preheating
DEF
Detector calibration
DEF
Detector test
N
Critical failure of a detector
3mA
Detector is locked (LOCKED mode)
22mA
Detector is overloaded (OVERLOAD mode)
22mA
Non-critical failure of a detector
N
Normal operation of the detector
N
Table 2: Output current in various modes of the module operation
N
– the output current is in proportion (4.. 20 mA) to the gas concentration reported by an appropriate
detector (4..20 mA),
DEF
– default current (3..22 mA) defined specifically for each separate transmission channel – see
Attachment [3].
The output current of ca. 2 mA measured in any out output line indicates a failure of the Sigma MOD AO
module.
4.3
Electric interfaces
Figure 6: Electric connections
s. 8|12
User Manual: POD-004-ENG R01