QSG_F600HP_425.00_EN_01_2021-01-25
16
/
34
DIGITAL INPUTS/OUTPUTS
The 24V DC power supply for the digital inputs can be provided by 2 means:
— The internal power supply of the device (0.3 A max)
— An external power supply provided by the customer.
Inputs default mode is PNP. NPN mode is available on request.
Relay board connector (J11) (option)
Characteristics
— Inputs
•
Activation: + 24 V DC
— Outputs
•
Dry contacts
•
60 V AC / DC max - 200 mA max
The device can be energized through the
J11
connector of the relay board (except if
internal supply option):
—
0 V to the pin
16
—
24 V DC to the pin
2
or
4
.
Pin number
Inputs / outputs
Description
1
Input 1
RESET
2
+ 24 V DC
Common
3
Input 2
START
4
+ 24 V DC
Common
5
Input 3
Program selection
6
Input 4
Program selection
7
Input 5
Program selection
8
Input 6
Program selection
9
Input 7
Program selection (programmable input)
10
Output
Common floating output
11
Output
Pass part
12
Output
Fail Part Up
13
Output
Fail Part Down
14
Output
Warning
15
Output
End of cycle
16
0 V
Ground