PN5212 / PN5320 User Manual
42
When you have finished making your configuration settings, click
Save
.
Power Off Delay
Sets the amount of time the PN5212 / PN5320 waits after the
Power Button is clicked (see
page 25), before it turns off the computer attached to the
corresponding outlet.
For the
System after AC Back
option (see below), after the
delay time expires, the PN5212 / PN5320 waits another fifteen
seconds, then shuts the computer down.
The default delay time is 15 seconds. The maximum delay time
is 999 seconds.
Shutdown Method
There are three choices for the Shutdown method. Drop down
the list to select a choice. The meaning of each choice is
described, below:
Wake on LAN:
This is a Safe Shutdown and Restart option. If
this is selected, when an Outlet is turned Off, the PN5212 /
PN5320 first sends a message to the computer telling it to
prepare for a shutdown; it then waits for the amount time set
in the
Power Off Delay field
to give the OS time to close down
before the computer is powered down to standby mode.
Likewise, when the Outlet is turned On, the PN5212 / PN5320
waits for the amount time set in the
Power On Delay
field,
then sends an Ethernet message to the computer connected
to the Outlet telling the computer to turn itself On.
Note:
For Safe Shutdown and Restart, the computer must be running
Windows (Windows 98 or higher), and the
Safe Shutdown
program
(available by download from our website), must be installed and
running on the computer.
System after AC Back:
This is a Safe Shutdown and Restart
option. If this is selected, when an Outlet is turned Off, the
PN5212 / PN5320 first sends a message to the computer
telling it to prepare for a shutdown; it then waits for the
amount time set in the
Power Off Delay
field to give the OS
time to close down before the computer is powered down.
When the Outlet is turned On, the PN5212 / PN5320 waits for
the amount time set in the
Power On Delay
field, then sends
power to the server. When the server receives the power, it
turns itself on.
Note:
For Safe Shutdown and Reboot, the computer must be running
Windows (Windows 98 or higher), and the
Safe Shutdown
program
(available by download from our website), must be installed and
running on the computer.
Kill the Power:
If this option is selected, the PN5212 / PN5320
waits for the amount time set in the
Power Off Delay
field, and
then turns the Outlet's power Off. Turning the power off
performs a cold (non-safe) shutdown.
MAC Address
In order to use either of the Safe Shutdown and Restart
methods the MAC address of the computer connected to the
outlet must be filled in here.
Server Diagnosis
These fields are used to set up an ICMP ping command to
check if the outlet is functioning properly. See
, page 31 for a further explanation.
Heading
Meaning
Summary of Contents for Altuscn PN5212
Page 1: ...Power Over the NET PN5212 PN5320 Power Distribution Unit User Manual www aten com ...
Page 19: ...Chapter 1 Introduction 5 Components Front View PN5320 NEMA PN5320 IEC 1 3 1 2 4 6 5 2 ...
Page 26: ...PN5212 PN5320 User Manual 12 3 5 4 2 1 SA0151 DTE ...
Page 36: ...PN5212 PN5320 User Manual 22 This Page Intentionally Left Blank ...
Page 98: ...PN5212 PN5320 User Manual 84 This Page Intentionally Left Blank ...
Page 104: ...PN5212 PN5320 User Manual 90 This Page Intentionally Left Blank ...
Page 110: ...PN5212 PN5320 User Manual 96 This Page Intentionally Left Blank ...
Page 150: ...PN5212 PN5320 User Manual 136 This Page Intentionally Left Blank ...