Chapter 2. Hardware Setup
13
Daisy Chaining
To manage even more outlets from the same single session as a standalone
PN5212 / PN5320, additional Power Over the NET™ devices can be daisy
chained, as described in the following three configurations.
Note:
The maximum distance between any two Power Over the NET™
devices
must not exceed 15 m; the total distance from the first station to
the last must not exceed 100 m.
PN5212 / PN5320 to PN5212 / PN5320
Up to 15 additional PN5212 / PN5320 stations can be daisy chained down from
the top level (master) device – allowing up to 320 outlets to be managed on a
complete installation. To daisy chain a PN5212 / PN5320, do the following:
1. Set the
RS-232/RS-485 switch
(see page 8), of the child device to the RS-
232 setting.
2. Use Cat 5e cable to connect the PON OUT port of the parent device to the
PON IN port of the child device.
3. Repeat the procedure for any additional devices you wish to connect.