ATEG Automation GmbH
|
Intzestraße 50
|
42859 Remscheid
|
Germany
|
Tel.: +49 (0)2191 / 591457-0
|
|
www.ateg.de
Datenblatt
Zeitrelais H3DT
H3DT
25
Power OFF-delay Timer
H3DT-H
• Set two time ranges with each Timer, from 0.1 to 12 seconds
for the S Series and from 1.0 to 120 seconds for the L Series.
LR
*
*
CSA conformance evaluation by UL.
For the most recent information on models that have been
certified for safety standards, refer to your OMRON website.
Ordering Information
List of Models
Model Structure
*
Certification is pending for DNV GL.
Specifications
Time Ranges
Ratings
Operating modes
Supply voltage
Control output
H3DT-H
S Series
(time range: 0.1 to 12 s)
L Series
(time range: 1.0 to 120 s)
Power OFF Delay
100 to 120 VAC
Contact output: SPDT
Model
H3DT-HCS
H3DT-HCL
200 to 240 VAC
Contact output: SPDT
H3DT-HDS
H3DT-HDL
24 to 48 VAC/DC
Contact output: SPDT
H3DT-HBS
H3DT-HBL
Model
Terminal block
Operating/resetting method
Output type
Mounting method
Safety standards
H3DT-H
6 terminals
Instantaneous operation/
time-limit reset
Relay, SPDT
DIN Track mounting
cULus
(UL 508 CSA C22.2 No. 14)
CCC
LR
DNV GL
*
EN 61812-1
IEC 60664-1 4 kV/2
S Series
L Series
Time range setting
x0.1
x1
x1
x10
Set time range
0.1 to 1.2 s
1 to 12 s
1 to 12 s
10 to 120 s
Power ON time
0.1 s min.
0.3 s min.
Scale numbers
12
Supply voltage
H3DT-HCS/-HCL
100 to 120 VAC, 50/60 Hz
H3DT-HDS/-HDL
200 to 240 VAC, 50/60 Hz
H3DT-HBS/-HBL
24 to 48 VAC/DC, 50/60 Hz
*
1
Allowable voltage fluctuation range
85% to 110% of rated voltage
Power
consumption
H3DT-HCS
At 120 VAC: 8.7 VA max.
H3DT-HCL
At 120 VAC: 8.8 VA max.
H3DT-HDS
At 240 VAC: 21.6 VA max.
H3DT-HDL
At 240 VAC: 21.7 VA max.
H3DT-HBS/-HBL
At 48 VAC: 1.0 VA max., at 24 VDC: 0.4 W max.
Timer operation starting voltage
30% or less of power supply voltage
Rated Insulation Voltage
250 VAC
Control output
Contact output, 5 A at 250 VAC with resistive load (cos
= 1),
5 A at 30 VDC with resistive load
Contact materials : Ag-alloy
(Recommended fuse: BLN5 (Littelfuse) or 0216005MXEP)
Ambient operating temperature
20 to 60
C (with no icing)
Storage temperature
40 to 70
C (with no icing)
Surrounding air operating humidity
25% to 85%
*
DC ripple: 20% max.
Erstellt am 04.09.2021 um 04:38 Uhr | Alle Angaben ohne Gewähr, Irrtümer und Änderungen vorbehalten!