Zeitrelais H3DT
H3DT
12
Power ON-delay Timer
H3DT-A
• Single Mode Timers with power ON delay operation.
LR
*
*
CSA conformance evaluation by UL.
For the most recent information on models that have been
certified for safety standards, refer to your OMRON website.
Ordering Information
List of Models
Model Structure
*
Certification is pending for DNV GL.
Specifications
Time Ranges
Ratings
Supply voltage
Control output
H3DT-A
24 to 240 VAC/DC
Contact output, DPDT (time-limit DPDT)
Model
H3DT-A2
Contact output, SPDT (time-limit SPDT)
H3DT-A1
Model
Operating modes
Terminal block
Output type
Mounting method
Safety standards
H3DT-A2
Power ON-delay
8 terminals
Relay, DPDT
DIN Track mounting
cULus
(UL508 CSA C22.2 No.14)
CCC
LR
DNV GL
*
EN61812-1
IEC60664-1 4 kV/2
H3DT-A1
6 terminals
Relay, SPDT
Time range setting
0.1 s
1 s
10 s
1 min
10 min
1 h
10 h
100 h
Set time range
0.1 to 1.2 s
1 to 12 s
10 to 120 s
1 to 12 min
10 to 120 min
1 to 12 h
10 to 120 h
100 to 1,200 h
Scale numbers
12
Power supply voltage
*
1
24 to 240 VAC/DC, 50/60 Hz
*
2
Allowable voltage fluctuation
range
85% to 110% of rated voltage
Power reset
Minimum power-OFF time: 0.1 s
Reset voltage
10% of rated voltage
*
3
Power
consumption
H3DT-A2
At 240 VAC: 2.2 VA max., at 240 VDC: 0.7 W max.,
at 24 VDC: 0.3 W max.
H3DT-A1
At 240 VAC: 1.8 VA max., at 240 VDC: 0.6 W max.,
at 24 VDC: 0.3 W max.
Rated Insulation Voltage
250 VAC
Control output
Contact output: 5 A at 250 VAC with resistive load (cos
= 1),
5 A at 30 VDC with resistive load,
0.15 A max. at 125 VDC with resistive load,
0.1A max. at 125 VDC with L/R of 7 ms.
The minimum applicable load is 10 mA at 5 VDC (P reference value).
Contact materials : Ag-alloy
(Recommended fuse: BLN5 (Littelfuse) or 0216005MXEP)
Ambient operating
temperature
20 to 60
C (with no icing)
Storage temperature
40 to 70
C (with no icing)
Surrounding air operating
humidity
25% to 85%
*1.
When using a 24-VDC power supply voltage,
there will be an inrush current of approximately
0.5 A. Allow for this inrush current when
turning ON and OFF the power supply to the
Timer with device with a solid-state output,
such as a sensor.
*2.
DC ripple: 20% max.
*3.
The power consumption is the value after the
Timer times out.