Installation & Servicing instructions ATAG iC-Range
26
Plume management kit
Figure 9.8.1.d
The appliance produces a white wisp of condensate (plumeing). This wisp of condensation is harmless, but
can be unattractive, particularly in the case of outlets in outside walls.
For wall terminals a plume management kit is available as an option (see fi g. 9.8.1.d).
Terminal position Plume Management Kit (mm)
1
Clearance no less than 200 mm from the lowest point of the balcony or overhang.
2
1.200 mm from an opening in a car port on the same wall i.e. door or window leading into dwelling.
3
The fl ue cannot be lower than 1.000 mm from the top of the light well due to the build up of combustion products.
4
1.200 mm between air intake and facing terminal.
5
Internal/external corners. The air intake clearance can be reduced to 150 mm providing the fl ue exhaust outlet has a 300 mm clearance.
6
600 mm distance to a boundary or surface facing a boundary, unless it will cause a nuisance.
BS 5440: Part 1 recommends that care is taken when siting terminals in relation to boundaries.
Notes:
1.
See also Notes on previous page.
2.
Plume kits running horizontally must have a 10° fall back to the boiler for proper disposal of condensate.
3.
For details on specifi c lengths see relevant chapter Dimensioning of the fl ue gas and air intake duct.
4.
A terminal must not be sited under a car port roof.
Figure 9.8.1.e
Summary of Contents for iC 24
Page 33: ...Installation Servicing instructions ATAG iC Range 33 Figure 10 7 a 10 9 Electrical diagram...
Page 56: ...Installation Servicing instructions ATAG iC Range 56 Annex C Short parts list...
Page 57: ...Installation Servicing instructions ATAG iC Range 57...
Page 58: ......
Page 59: ......
Page 60: ......
Page 61: ......