FIREPLACE INSTALLATION

SELECTING LOCATION

To determine safest and most efficient location for fireplace, you 

must take into consideration the following guidelines:
1.  Location must allow for proper clearances (see Figures 1 and 2).
2.  Consider a location where fireplace will not be affected by drafts, 

air conditioning ducts, windows or doors.

3.  A location that avoids cutting of joists or roof rafters will make 

installation easier.

4.  An outside air kit is available with this fireplace (see Optional 

Outside Air Kit on page 7).

MINIMUM CLEARANCE TO COMBUSTIBLES

Back and sides of fireplace                                      3/4" minimum*
Floor**                                                                       0" minimum
Perpendicular wall to opening                                   12" minimum
Top spacers                                                                0" minimum
Mantel clearances                                            see Mantels, page 6 
Chimney outer pipe surface                                        1" minimum

* Not required at nailing flanges 

** See step 2 of Framing

 WARNING: DO NOT PACK REQUIRED AIR SPACES 

WITH INSULATION OR OTHER MATERIALS.

Minimum/Maximum Chimney Height

The minimum height of the chimney, measured from the base of 

the fireplace to the flue gas outlet of the termination, is 14.5 feet for 

straight flue or a flue with one elbow set. The maximum distance 

between elbows is 6 feet. For systems with two elbow sets, the 

minimum height is 22 feet. The maximum height of any system is 

50 feet. This measurement includes the fireplace, chimney sections 

and the height of the termination assembly at the level of the flue 

gas outlet (see Figure 18, page 11).

Minimum/Maximum Chimney Height for Outdoor Installation

The minimum height of the chimney, measured from the base of the 

fireplace to the flue gas outlet of the termination, is 8 feet (minimum 

of 4 feet of chimney pipe sections required for outdoor installation).

Figure 1 - Framing Dimensions

Figure 2 - Corner Installation

FRAMING

1.  Frame opening for fireplace using dimensions shown in Figures 

1 and 2.

Note:

 When the fireplace is framed, the header has to be turned 

on the vertical edge to maintain proper clearance.

2.  If fireplace is to be installed directly on carpeting, tile or any 

combustible material other than wood flooring, fireplace must 

be installed upon a metal or wood panel extending full width and 

depth of fireplace.

3.  Set fireplace directly in front of this opening and slide unit back 

until nailing flanges touch side framing.

4.  Check level of fireplace and shim with sheet metal if necessary.
5.  Before securing fireplace to prepared framing, ember protector 

must be placed between hearth extension (not included) and 

under bottom front edge of fireplace to protect against glowing 

embers falling through. If fireplace is to be installed on a raised 

platform, a Z-type ember protector (not included) must be fabri-

cated to fit your required platform height. Ember protector should 

extend under fireplace a minimum of 1 

1

/

2

". Ember protector 

should be made of galvanized sheet metal (28 gauge minimum) 

to prevent corrosion.

6.  Using screws or nails, secure fireplace to framing through flanges 

located on sides of fireplace.

19 

1

/

2

" (496 mm)  

28"

(712 mm)  

59 

3

/

8

"

(1509 mm)  

83 

7

/

8

" (2131 mm)  

Maintain 

3

/

4

"

Clearance at

Sides and Back

of Fireplace  

49 

3

/

4

"

(1264 mm)  

47 

1

/

4

"

(1201 mm)  

23 

1

/

2

"

(597 mm)  

2 x 4 Header 

Turned on 

the Vertical 

Edge

Summary of Contents for Tuscan42P2

Page 1: ...as the municipal building department fire department etc should be contacted before installation to determine the need to obtain a permit POUR LE CANADA L autorité compétente comme le service municipal du bâtiment les pompiers etc doit être contacté avant l installation afin de déterminer la nécessité d obtenir un permis This appliance may be installed in an aftermarket permanently located manufac...

Page 2: ...system and damper control b Use of any component part not manufactured or approved by IHP in combination with an IHP fireplace system Proper installation is the most important step in ensuring safe and continuous operation of the fireplace Consult the local building codes as to the particular requirements concerned with the installation of all factory built fireplaces NOTICE The firebox canopy hoo...

Page 3: ...ignificanthazard IMPORTANT See appendix A page 21 for additional information regarding draft requirements smoking causes and troubleshooting WARNING BURNING IMPROPER FUEL I E CHARCOAL CAN RESULT IN CARBON MONOXIDE POISONING WHICH MAY LEAD TO DEATH Carbon Monoxide Poisoning Early signs of carbon monoxidepoisoningresemblethefluwithheadaches dizziness or nausea If you have these signs get fresh air a...

Page 4: ... 2 572 mm INNER DIA 12 3 8 315 mm 5 8 16 mm 36 915 mm 48 1220 mm OUTER DIA 15 381 mm 24 610 mm 8 204 mm 42 1067 mm 41 1042 mm 48 1067 mm 3 4 19 mm AIR SPACE BACK AND SIDES GAS LINE KNOCK OUTS GAS LINE KNOCK OUTS ELECTRICAL OUTLET RIGHT SIDE LEFT SIDE AIR KIT KNOCK OUT 6 3 4 172 mm 10 5 8 270 mm 12 5 8 321 mm 10 5 8 270 mm 14 1 4 362 mm 16 1 4 413 mm 12 305 mm 8 1 8 207 mm 2 1 2 64 mm 29 1 2 750 mm...

Page 5: ... Installation The minimum height of the chimney measured from the base of the fireplace to the flue gas outlet of the termination is 8 feet minimum of 4 feet of chimney pipe sections required for outdoor installation Figure 1 Framing Dimensions Figure 2 Corner Installation FRAMING 1 Frame opening for fireplace using dimensions shown in Figures 1 and 2 Note When the fireplace is framed the header h...

Page 6: ...floor construction in front of fireplace Fab ricate a hearth extension using a material which meets the following specifications a layer of noncombustible inorganic material having a thermal conductivity of k 84 BTU IN FT2 HR F or less at 1 thick For example if material selected has a k factor of 0 25 such as glass fiber the following formula would apply 0 25 x 1 0 0 30 thickness required 0 84 The...

Page 7: ...2 18 24 36 and 48 snap lock double wall pipe segments planned for maximum adaptability to individual site requirements Actual lengths gained after fitting overlaps must be taken into consideration lineal gain and are given in lineal gain chart see Figure 6 Lineal gain is actual measurable length of a part after two or more parts are connected Figure 6 Lineal Gain Hemmed End 8 Stainless Inner Pipe ...

Page 8: ... a vertical chimney pipe supported ONLY by the fireplace must not exceed 20 feet Chimney heights above 20 feet must be supported USING ELBOW OFFSET 30E 12DMO 8DMR To clear overhead obstructions you may offset your chimney system using 30E 12DMO 8DMR 30 Offset return elbow A section or sections of chimney may be used between offsets and return elbow Transition pipe must be used after elbow offset i...

Page 9: ...2 3 4 1 1 1 38 1 2 75 1 2 1 1 3 39 1 4 76 3 4 1 1 1 1 41 1 2 80 1 2 1 1 2 1 42 1 4 81 3 4 1 1 1 1 44 1 2 85 3 4 1 1 1 1 1 45 1 4 87 1 1 1 1 47 1 2 91 1 1 2 1 48 1 4 92 1 4 1 1 2 49 3 4 94 3 4 1 1 2 1 1 52 98 3 4 1 1 1 4 53 1 2 101 1 4 1 1 1 2 54 1 4 102 3 4 1 1 1 1 55 3 4 105 1 4 1 1 3 1 56 1 2 1061 2 1 1 1 2 58 3 4 110 1 2 1 1 2 2 59 1 2 111 3 4 1 1 1 1 1 60 1 4 113 1 1 2 61 3 4 115 3 4 1 1 1 1 2...

Page 10: ...lete separation from one floor space to an other or attic space as required by most codes When double wall pipe passes through a framed opening into an attic space firestop must be placed into an attic floor as shown in Figure 11 Figure 10 Firestop Spacer with Living Space Above Ceiling Figure 11 Firestop Spacer with Attic Space Above Ceiling IMPORTANT NOTICE When penetrating a ceiling into an att...

Page 11: ...ipe and slide down until it is snug against open edge of flashing see Figure 14 Use SC1 for all round termina tions Apply waterproof caulk around perimeter of collar to provide a proper seal Figure 14 Storm Collar Chimney Pipe Waterproof Caulk Storm Collar Flashing Terminations Spark Arrestor Fireplace system must be terminated with listed round top or chase terminations In any case refer to insta...

Page 12: ...aised platform add height Provide sufficient gas line into fireplace chamber for fitting OPTIONAL GAS LINE INSTALLATION Figure 18 Typical Residential Installations VENTING INSTALLATION Continued connection see Figure 20 page 13 Note Secure incoming gas line to wood framing to provide rigidity for threaded end 4 Repack insulation around gas line and into sleeve opening Seal any gaps between gas lin...

Page 13: ...NING FIREPLACESEQUIPPEDWITHDOORS SHOULD BE OPERATED ONLY WITH DOORS FULLY OPEN OR DOORS FULLY CLOSED IF DOORS ARE LEFTPARTLYOPEN GASANDFLAMEMAYBEDRAWN OUT OF THE FIREPLACE OPENING CREATING RISKS OF BOTH FIRE AND SMOKE WARNING Discontinue use of the appliance imme diately if doors are damaged and contact a qualified installer for repair Only doors certified with the appliance shall be used WARNING ...

Page 14: ...ng guidelines instructions and warranty informa tion please refer to your homeowner s guide or contact your dealer Access Panel OPEN CLOSE Damper Handle Outside Air Kit Handle Keyway Slot Handle Retainer REPLACEMENT PARTS See Pages 16 to 18 for a complete replacement parts list Use only parts supplied from the manufacturer Normally all parts should be ordered through your IHP distributor or dealer...

Page 15: ...T 36 Section Hi Temp Double Wall Pipe Snap Lock F0885 48 8HT 48 Section Hi Temp Double Wall Pipe Snap Lock F0886 30E 8HT 30 Degree Hi Temp Offset and Return F0887 12S 8HT Hi Temp Chimney Support For Use With Chimney Heights In Excess of 30 F0888 RT 8HT Hi Temp Round Top with Mesh Screen F0889 RTT 8HT Hi Temp Round Top with Mesh Screen and Slip Sec tion F0890 RLT 8HT Hi Temp Round Top with Louvered...

Page 16: ...s com 127051 01_E 16 PARTS WOOD BURNING FIREPLACE MODELS 9 24 16 31 25 16 4 30 32 19 12 23 20 28 17 8 1 5 21 2 18 11 14 3 13 22 10 6 35 29 7 33 34 26 27 15 MODEL NO CATALOG NO Tuscan42P2 F0542 Tuscan42P3 F0543 ...

Page 17: ...Liner 1 11 See Page 18 Rear Refractory Brick Liner 1 12 See Page 18 Bottom Rear Refractory Brick Liner 1 13 See Page 18 Bottom Front Refractory Brick Liner 1 14 J3972 Firebox Support Leg 4 15 Damper Can Collar 1 16 J8013 Kit Screen Assembly 1 17 Firebox Top Assembly 1 18 J3980 Air Kit Door Assembly 1 19 Face Weldment 1 20 J4471 Air Deflector 1 21 Fireplace Top Insulation 1 22 Access Panel 1 23 J45...

Page 18: ... J4508 Bottom Front Refractory White Brick 1 PARTS WOOD BURNING FIREPLACE MODELS TUSCAN42P2 AND TUSCAN42P3 Rear Left Side Front Bottom Bottom Right Side MODEL NO CATALOG NO Tuscan42P2 F0542 Tuscan42P3 F0543 ACCESSORIES REFRACTORY STAIN KITS Use the refractory stain kits to give white refractory panels a new look Kit includes foam roller handle paint tray and one can of stain Available stain colors...

Page 19: ...ection Hi Temp Double Wall Pipe Snap Lock F0883 24 8HT 24 Section Hi Temp Double Wall Pipe Snap Lock F0884 36 8HT 36 Section Hi Temp Double Wall Pipe Snap Lock F0885 48 8HT 48 Section Hi Temp Double Wall Pipe Snap Lock 30 OFFSET AND RETURN F0900 30E 8DM 30 Degree Offset and Return F0886 30E 8HT 30 Degree Hi Temp Offset and Return F1908 30E 12DMO 8DMR 30 Elbow Set 12 to 8 Craftsman 42 F2199 30E 12H...

Page 20: ...on F0923 ETLO 8DM Square Top with Mesh and Slip Section MESH SQUARE TOP TERMINATION F0922 ETO 8DM Square Top with Mesh MESH SQUARE TOP TERMINATION WITH SLIP SECTION F0923 ETLO 8DM Square Top with Mesh and Slip Section STAINLESS STEEL HOOD Required when installing a vent free gas log in this fireplace F1053 HS42 42 Stainless Steel Hood w 4 Brow DRAIN PAN F1090 DP42 Drain Pan FIRESTOP THIMBLE F0911 ...

Page 21: ...ing the proper venting system for your installation American National Standards Institute ANSI NFPA 211 Standard for Chimneys Fireplaces Vents and Solid Fuel Burning Appli ances See Draft Section A chimney or vent shall be so designed and constructed to develop a flow sufficient to completely remove all flue and vent gases to the outside atmosphere The venting system shall satisfy the draft requir...

Page 22: ...The best location to install your appliance is determined by consid ering the location of windows doors and the traffic flow in the room where the appliance is located allowing space in front of the unit for the hearth extension and the mantel and taking into consideration the location of the hot air ducts some models outside air kit and chimney Ifpossible youshouldchoosealocationwherethechimneywi...

Page 23: ...or propane gas Fuel products with abnormal burning characteristics including but not limited to fuel such as driftwood coal or plywood and wood products using a binder may burn at excessive temperatures and may cause damage to the Product or may cause it to function improperly c damages caused by failing to provide proper maintenance and service in accordance with the instructions provided with th...

Page 24: ...01 Innovative Hearth Products reserves the right to make changes at any time without notice in design materials specifications prices and also to discontinue colors styles and products Consult your local distributor for fireplace code information Printed in U S A 2013 Innovative Hearth Products LLC P N 127051 01 Rev E 05 2017 1508 Elm Hill Pike Suite 108 Nashville TN 37210 ...

Reviews: