Astria Fireplaces Tuscan42P2 Assembly, Installation And Operation Instructions Download Page 21

Astria.us.com

127051-01_E

21

APPENDIX A

Draft Requirements

Your wood-burning appliance is dependent upon a properly func-

tioning chimney for optimum performance. It is important to match 

the wood-burning appliance to the chimney. The chimney has two 

functions: 

1. It draws combustion air into the appliance (without air, no fuel 

will burn) and 

2. It exhausts combustion by-products. Your new appliance is what 

is known as a “natural draft” appliance. 

The appliance depends solely on the natural draft of the chimney 

system to draw combustion air into the unit. Draft is the force that 

moves air from the appliance up into the chimney. The amount of 

draft in your chimney depends on the length of the chimney, local 

geography, nearby obstructions and other factors. Too much draft 

may cause excessive temperatures in the appliance (overfiring). Slow 

or inadequate draft equals poor combustion and possible smoking 

problems. The following are some conditions that may contribute 

to poor chimney draft: 

1. A chimney too large for your appliance. 

2. A chimney with not enough height to produce adequate draft.

3. A chimney with excessive height (this may allow exhaust to cool 

too much before exiting, which will stall the rate the exhaust exits). 

4. Offsets in the venting system are too restrictive 

(see Chimney 

Guidelines

).

Inadequate draft will cause the appliance to leak smoke into the room 

through the wood-burning appliance and the chimney connector joints. 

Excessive draft may cause an uncontrollable burn or a glowing red 

appliance or chimney part. 

Overfiring Damage -

 If the appliance or chimney connector glows, 

you are overfiring. Other symptoms may include: Cracking, warping 

or burning out of components, plated accessories may turn color, 

appliance glass may develop a haze, which will not come off with 

cleaning.
Overfiring of a appliance is a condition where excessive tempera-

tures are reached, beyond the design capabilities of the appliance. 

The damage that occurs from overfiring is not covered under the 

manufacturer’s limited warranty.
Also see Troubleshooting on Page 22.

Selecting the Proper Venting System

The appliance is merely one component of a larger system. The 

other equally important component is the venting system. This is 

necessary for achieving the required flow of combustion air to the fire 

chamber and for safely removing unwanted combustion by products 

from the appliance.
If the venting system’s design does not promote these ends, the system 

may not function properly. Poorly functioning venting systems may 

create performance problems as well as be a safety hazard.  

A draft 

test should read greater than .04’ W.C. (inches water column) and 

less than .08” W.C.

  As per NFPA-211 standard, the installer must 

 WARNING 

Neither the manufacturer nor the seller warrants “smoke 

free” operation nor are we responsible for inadequate 

system draft caused by mechanical systems, general 

construction conditions, inadequate chimney heights, 

adverse wind conditions and/or unusual environmental 

factors or conditions beyond our control. 

take into account all variables within the installation and install the 

appliance in such a manner that satisfies the draft requirements of 

the appliance.  See Chimney Guidelines to assist you in selecting the 

proper venting system for your installation.

American National Standards Institute ANSI/NFPA 211, Standard 

for Chimneys, Fireplaces, Vents, and Solid Fuel-Burning Appli-

ances - See Draft Section:

  A chimney or vent shall be so designed 

and constructed to develop a flow sufficient to completely remove all 

flue and vent gases to the outside atmosphere. The venting system 

shall satisfy the draft requirements of the connected appliance in 

accordance with the manufacturer’s instructions.

Chimney Guidelines:

•  Most wood-burning appliances requires approximately 12 feet 

minimum of “effective draw” provided by the venting system.  As a 

rule of thumb, every 90 degree total direction change in the venting 

will result in a loss of approximately 5 feet of “effective draw.”  

Example: If two 45 degree offsets are used, subtract 5 feet from 

the actual vertical vent height to determine your “effective draw.”  

In this case if you had 14 feet of vertical vent, the effective draw 

would only be approximately 9 feet (14 ft. - 5 ft. = 9 ft.), therefore 

it may be necessary to add additional height to the venting system.

•  Do not install an offset within the first two feet above the flue outlet 

on the appliance.

•  In well insulated and weather tight homes, it may be difficult to 

establish a good draft up your chimney. The poor draft is caused 

by a shortage of air in the house.  In this situation an Outside Air 

Kit may need to be installed (See Negative Pressure Warning be-

low and Outside Combustion Air in the Installation and Operation 

manual).

Negative Pressure Warning

These appliances are not designed to be operated in a negative 

pressure. In very airtight homes with large kitchen exhaust fans, 

furnace cold air returns, fresh air exchange systems and any other 

air system in close proximity to the heating appliance may create a 

negative pressure in the same room as the heating appliance. This can 

create dangerous back drafting of the appliance and chimney joints, 

drawing combustion by-products into the home. Be sure your home 

has adequate makeup air to eliminate negative pressures caused by 

the above-mentioned sources. Outside air connected to the appliance 

probably will not resolve such a problem as the appliance is not the 

source of negative pressure. IHP accepts no liability for damages 

resulting from negative pressures described here.

Ventilation Requirements -

 Provide adequate air for combustion. 

The fresh air requirements of this appliance must be met within the 

space where it will be installed. Ventilation is essential when using 

a solid-fuel-burning appliance.  In well insulated and weather tight 

homes, it may be difficult to establish a good draft up the chimney 

(caused by a shortage of air in the home). The lack of air is caused 

by many common household appliances which exhaust air from the 

home (such as a furnace, heat pump, air conditioner, clothes dryer, 

exhaust fans, fireplaces, and other fuel burning appliances). Also, the 

combustion process of this appliance uses oxygen from inside the 

dwelling.  If the available fresh air delivery in the dwelling is insufficient 

to support the demands of these appliances, problems can result 

(i.e. excessive negative pressure can develop in the dwelling which 

will affect the rate at which this appliance can draft thus resulting 

in performance problems or smoking.  To correct this problem it 

may help to open a window (preferably on the windward side of the 

house) or install an outside air kit.

Summary of Contents for Tuscan42P2

Page 1: ...as the municipal building department fire department etc should be contacted before installation to determine the need to obtain a permit POUR LE CANADA L autorité compétente comme le service municipal du bâtiment les pompiers etc doit être contacté avant l installation afin de déterminer la nécessité d obtenir un permis This appliance may be installed in an aftermarket permanently located manufac...

Page 2: ...system and damper control b Use of any component part not manufactured or approved by IHP in combination with an IHP fireplace system Proper installation is the most important step in ensuring safe and continuous operation of the fireplace Consult the local building codes as to the particular requirements concerned with the installation of all factory built fireplaces NOTICE The firebox canopy hoo...

Page 3: ...ignificanthazard IMPORTANT See appendix A page 21 for additional information regarding draft requirements smoking causes and troubleshooting WARNING BURNING IMPROPER FUEL I E CHARCOAL CAN RESULT IN CARBON MONOXIDE POISONING WHICH MAY LEAD TO DEATH Carbon Monoxide Poisoning Early signs of carbon monoxidepoisoningresemblethefluwithheadaches dizziness or nausea If you have these signs get fresh air a...

Page 4: ... 2 572 mm INNER DIA 12 3 8 315 mm 5 8 16 mm 36 915 mm 48 1220 mm OUTER DIA 15 381 mm 24 610 mm 8 204 mm 42 1067 mm 41 1042 mm 48 1067 mm 3 4 19 mm AIR SPACE BACK AND SIDES GAS LINE KNOCK OUTS GAS LINE KNOCK OUTS ELECTRICAL OUTLET RIGHT SIDE LEFT SIDE AIR KIT KNOCK OUT 6 3 4 172 mm 10 5 8 270 mm 12 5 8 321 mm 10 5 8 270 mm 14 1 4 362 mm 16 1 4 413 mm 12 305 mm 8 1 8 207 mm 2 1 2 64 mm 29 1 2 750 mm...

Page 5: ... Installation The minimum height of the chimney measured from the base of the fireplace to the flue gas outlet of the termination is 8 feet minimum of 4 feet of chimney pipe sections required for outdoor installation Figure 1 Framing Dimensions Figure 2 Corner Installation FRAMING 1 Frame opening for fireplace using dimensions shown in Figures 1 and 2 Note When the fireplace is framed the header h...

Page 6: ...floor construction in front of fireplace Fab ricate a hearth extension using a material which meets the following specifications a layer of noncombustible inorganic material having a thermal conductivity of k 84 BTU IN FT2 HR F or less at 1 thick For example if material selected has a k factor of 0 25 such as glass fiber the following formula would apply 0 25 x 1 0 0 30 thickness required 0 84 The...

Page 7: ...2 18 24 36 and 48 snap lock double wall pipe segments planned for maximum adaptability to individual site requirements Actual lengths gained after fitting overlaps must be taken into consideration lineal gain and are given in lineal gain chart see Figure 6 Lineal gain is actual measurable length of a part after two or more parts are connected Figure 6 Lineal Gain Hemmed End 8 Stainless Inner Pipe ...

Page 8: ... a vertical chimney pipe supported ONLY by the fireplace must not exceed 20 feet Chimney heights above 20 feet must be supported USING ELBOW OFFSET 30E 12DMO 8DMR To clear overhead obstructions you may offset your chimney system using 30E 12DMO 8DMR 30 Offset return elbow A section or sections of chimney may be used between offsets and return elbow Transition pipe must be used after elbow offset i...

Page 9: ...2 3 4 1 1 1 38 1 2 75 1 2 1 1 3 39 1 4 76 3 4 1 1 1 1 41 1 2 80 1 2 1 1 2 1 42 1 4 81 3 4 1 1 1 1 44 1 2 85 3 4 1 1 1 1 1 45 1 4 87 1 1 1 1 47 1 2 91 1 1 2 1 48 1 4 92 1 4 1 1 2 49 3 4 94 3 4 1 1 2 1 1 52 98 3 4 1 1 1 4 53 1 2 101 1 4 1 1 1 2 54 1 4 102 3 4 1 1 1 1 55 3 4 105 1 4 1 1 3 1 56 1 2 1061 2 1 1 1 2 58 3 4 110 1 2 1 1 2 2 59 1 2 111 3 4 1 1 1 1 1 60 1 4 113 1 1 2 61 3 4 115 3 4 1 1 1 1 2...

Page 10: ...lete separation from one floor space to an other or attic space as required by most codes When double wall pipe passes through a framed opening into an attic space firestop must be placed into an attic floor as shown in Figure 11 Figure 10 Firestop Spacer with Living Space Above Ceiling Figure 11 Firestop Spacer with Attic Space Above Ceiling IMPORTANT NOTICE When penetrating a ceiling into an att...

Page 11: ...ipe and slide down until it is snug against open edge of flashing see Figure 14 Use SC1 for all round termina tions Apply waterproof caulk around perimeter of collar to provide a proper seal Figure 14 Storm Collar Chimney Pipe Waterproof Caulk Storm Collar Flashing Terminations Spark Arrestor Fireplace system must be terminated with listed round top or chase terminations In any case refer to insta...

Page 12: ...aised platform add height Provide sufficient gas line into fireplace chamber for fitting OPTIONAL GAS LINE INSTALLATION Figure 18 Typical Residential Installations VENTING INSTALLATION Continued connection see Figure 20 page 13 Note Secure incoming gas line to wood framing to provide rigidity for threaded end 4 Repack insulation around gas line and into sleeve opening Seal any gaps between gas lin...

Page 13: ...NING FIREPLACESEQUIPPEDWITHDOORS SHOULD BE OPERATED ONLY WITH DOORS FULLY OPEN OR DOORS FULLY CLOSED IF DOORS ARE LEFTPARTLYOPEN GASANDFLAMEMAYBEDRAWN OUT OF THE FIREPLACE OPENING CREATING RISKS OF BOTH FIRE AND SMOKE WARNING Discontinue use of the appliance imme diately if doors are damaged and contact a qualified installer for repair Only doors certified with the appliance shall be used WARNING ...

Page 14: ...ng guidelines instructions and warranty informa tion please refer to your homeowner s guide or contact your dealer Access Panel OPEN CLOSE Damper Handle Outside Air Kit Handle Keyway Slot Handle Retainer REPLACEMENT PARTS See Pages 16 to 18 for a complete replacement parts list Use only parts supplied from the manufacturer Normally all parts should be ordered through your IHP distributor or dealer...

Page 15: ...T 36 Section Hi Temp Double Wall Pipe Snap Lock F0885 48 8HT 48 Section Hi Temp Double Wall Pipe Snap Lock F0886 30E 8HT 30 Degree Hi Temp Offset and Return F0887 12S 8HT Hi Temp Chimney Support For Use With Chimney Heights In Excess of 30 F0888 RT 8HT Hi Temp Round Top with Mesh Screen F0889 RTT 8HT Hi Temp Round Top with Mesh Screen and Slip Sec tion F0890 RLT 8HT Hi Temp Round Top with Louvered...

Page 16: ...s com 127051 01_E 16 PARTS WOOD BURNING FIREPLACE MODELS 9 24 16 31 25 16 4 30 32 19 12 23 20 28 17 8 1 5 21 2 18 11 14 3 13 22 10 6 35 29 7 33 34 26 27 15 MODEL NO CATALOG NO Tuscan42P2 F0542 Tuscan42P3 F0543 ...

Page 17: ...Liner 1 11 See Page 18 Rear Refractory Brick Liner 1 12 See Page 18 Bottom Rear Refractory Brick Liner 1 13 See Page 18 Bottom Front Refractory Brick Liner 1 14 J3972 Firebox Support Leg 4 15 Damper Can Collar 1 16 J8013 Kit Screen Assembly 1 17 Firebox Top Assembly 1 18 J3980 Air Kit Door Assembly 1 19 Face Weldment 1 20 J4471 Air Deflector 1 21 Fireplace Top Insulation 1 22 Access Panel 1 23 J45...

Page 18: ... J4508 Bottom Front Refractory White Brick 1 PARTS WOOD BURNING FIREPLACE MODELS TUSCAN42P2 AND TUSCAN42P3 Rear Left Side Front Bottom Bottom Right Side MODEL NO CATALOG NO Tuscan42P2 F0542 Tuscan42P3 F0543 ACCESSORIES REFRACTORY STAIN KITS Use the refractory stain kits to give white refractory panels a new look Kit includes foam roller handle paint tray and one can of stain Available stain colors...

Page 19: ...ection Hi Temp Double Wall Pipe Snap Lock F0883 24 8HT 24 Section Hi Temp Double Wall Pipe Snap Lock F0884 36 8HT 36 Section Hi Temp Double Wall Pipe Snap Lock F0885 48 8HT 48 Section Hi Temp Double Wall Pipe Snap Lock 30 OFFSET AND RETURN F0900 30E 8DM 30 Degree Offset and Return F0886 30E 8HT 30 Degree Hi Temp Offset and Return F1908 30E 12DMO 8DMR 30 Elbow Set 12 to 8 Craftsman 42 F2199 30E 12H...

Page 20: ...on F0923 ETLO 8DM Square Top with Mesh and Slip Section MESH SQUARE TOP TERMINATION F0922 ETO 8DM Square Top with Mesh MESH SQUARE TOP TERMINATION WITH SLIP SECTION F0923 ETLO 8DM Square Top with Mesh and Slip Section STAINLESS STEEL HOOD Required when installing a vent free gas log in this fireplace F1053 HS42 42 Stainless Steel Hood w 4 Brow DRAIN PAN F1090 DP42 Drain Pan FIRESTOP THIMBLE F0911 ...

Page 21: ...ing the proper venting system for your installation American National Standards Institute ANSI NFPA 211 Standard for Chimneys Fireplaces Vents and Solid Fuel Burning Appli ances See Draft Section A chimney or vent shall be so designed and constructed to develop a flow sufficient to completely remove all flue and vent gases to the outside atmosphere The venting system shall satisfy the draft requir...

Page 22: ...The best location to install your appliance is determined by consid ering the location of windows doors and the traffic flow in the room where the appliance is located allowing space in front of the unit for the hearth extension and the mantel and taking into consideration the location of the hot air ducts some models outside air kit and chimney Ifpossible youshouldchoosealocationwherethechimneywi...

Page 23: ...or propane gas Fuel products with abnormal burning characteristics including but not limited to fuel such as driftwood coal or plywood and wood products using a binder may burn at excessive temperatures and may cause damage to the Product or may cause it to function improperly c damages caused by failing to provide proper maintenance and service in accordance with the instructions provided with th...

Page 24: ...01 Innovative Hearth Products reserves the right to make changes at any time without notice in design materials specifications prices and also to discontinue colors styles and products Consult your local distributor for fireplace code information Printed in U S A 2013 Innovative Hearth Products LLC P N 127051 01 Rev E 05 2017 1508 Elm Hill Pike Suite 108 Nashville TN 37210 ...

Reviews: