Astria Fireplaces Tuscan42P2 Assembly, Installation And Operation Instructions Download Page 10

Astria.us.com

127051-01_E

10

VENTING INSTALLATION 

Continued

Pitch

Slope Opening "A" 

Max. 

Used Flashing 

Model No. 

Flat

15"

V6F-8DM

0-6/12

26.6°

16 

1

/

8

"

V6F-8DM

6/12- 12/12

45.0°

20 

3

/

8

"

V12F-8DM

Figure 12 - Roof Opening Measurements

FLASHING INSTALLATION (V6F-8DM OR V12F-8DM)

Determine flashing to be used with roof opening chart. Slide flashing 

over pipe until base is flat against roof. Replace as many shingles as 

needed to cover exposed area and flashing base. Secure in position 

by nailing through shingles (see Figure 13). DO NOT NAIL THROUGH 

FLASHING CONE.

Installing Flashing on a Metal Roof

When installing flashing on a metal roof, it is required that putty tape 

be used between flashing and roof. Flashing must be secured to roof 

using #8 x 3/4" screws and then sealed with roof coating to prevent 

leakage through screw holes. A roof coating must also be applied 

around perimeter of flashing to provide a proper seal.

Figure 13 - Flashing Installation

Nail Only Outer 

Perimeter of 

Flashing

Storm Collar

Underlap Shingles at 

Bottom

Flashing Cone

Overlap 

Shingles Top 

and Sides Only

FIRESTOP SPACERS (3600FS-8DM-1)

Firestop spacers are required at each point where chimney penetrates 

a floor space. Their purpose is to establish and maintain required 

clearance between chimney and combustible materials. When pipe 

passes through a framed opening into a living space above, firestop 

must be placed onto ceiling from below as shown in Figure 10.
They also provide complete separation from one floor space to an-

other or attic space as required by most codes. When double wall 

pipe passes through a framed opening into an attic space, firestop 

must be placed into an attic floor as shown in Figure 11.

Figure 10 - Firestop Spacer with Living Space Above Ceiling

Figure 11 - Firestop Spacer with Attic Space Above Ceiling

IMPORTANT NOTICE 

When penetrating a ceiling into an attic, a firestop thimble 

(38FST or FST30) is required to avoid intrusion by insulation 

and recommended to negotiate a joist (see Figure 11a).

30"

(76.2 cm)

Minimum Measurements

Opening "A"

14 

3

/

8

"

(48.3 cm)

1"

(2.54

cm)

1"

(2.54

cm)

1"

(2.54 cm)

Existing 

Ceiling Frame

Firestop 

Spacer

Screws or Staples 

(Min. of 8)

Firestop Spacer

Screws or Staples 

(Min. of 8)

Existing 

Ceiling 

Frame

Figure 11a - Firestop Thimble

Thimble 38FST 

or FST30

Firestop

PENETRATING ROOF

To maintain a 1" clearance to pipe on a roof with a pitch, a rectangular 

opening must be cut.
1.  Determine center point where pipe will penetrate the roof.
2.  Determine center point of the roof. Pitch is the distance the roof drops 

over a given span, usually 12". A 6/12 pitch means that the roof drops 

6" for each 12" measure horizontally down from roof rafters.

3.  Use roof opening chart (Figure 12) to determine correct opening 

length and flashing required.

4.  Remove shingles around opening measured. Cut out this section.
5.  Add next sections of pipe until end penetrates roof line. Check to 

see that proper clearances are maintained. Extend chimney by add-

ing sections of double wall pipe until pipe is minimum of 30" above 

highest point of roof cutout. Termination and chimney must extend 

a minimum of 36" above highest point where it passes through roof.

Summary of Contents for Tuscan42P2

Page 1: ...as the municipal building department fire department etc should be contacted before installation to determine the need to obtain a permit POUR LE CANADA L autorité compétente comme le service municipal du bâtiment les pompiers etc doit être contacté avant l installation afin de déterminer la nécessité d obtenir un permis This appliance may be installed in an aftermarket permanently located manufac...

Page 2: ...system and damper control b Use of any component part not manufactured or approved by IHP in combination with an IHP fireplace system Proper installation is the most important step in ensuring safe and continuous operation of the fireplace Consult the local building codes as to the particular requirements concerned with the installation of all factory built fireplaces NOTICE The firebox canopy hoo...

Page 3: ...ignificanthazard IMPORTANT See appendix A page 21 for additional information regarding draft requirements smoking causes and troubleshooting WARNING BURNING IMPROPER FUEL I E CHARCOAL CAN RESULT IN CARBON MONOXIDE POISONING WHICH MAY LEAD TO DEATH Carbon Monoxide Poisoning Early signs of carbon monoxidepoisoningresemblethefluwithheadaches dizziness or nausea If you have these signs get fresh air a...

Page 4: ... 2 572 mm INNER DIA 12 3 8 315 mm 5 8 16 mm 36 915 mm 48 1220 mm OUTER DIA 15 381 mm 24 610 mm 8 204 mm 42 1067 mm 41 1042 mm 48 1067 mm 3 4 19 mm AIR SPACE BACK AND SIDES GAS LINE KNOCK OUTS GAS LINE KNOCK OUTS ELECTRICAL OUTLET RIGHT SIDE LEFT SIDE AIR KIT KNOCK OUT 6 3 4 172 mm 10 5 8 270 mm 12 5 8 321 mm 10 5 8 270 mm 14 1 4 362 mm 16 1 4 413 mm 12 305 mm 8 1 8 207 mm 2 1 2 64 mm 29 1 2 750 mm...

Page 5: ... Installation The minimum height of the chimney measured from the base of the fireplace to the flue gas outlet of the termination is 8 feet minimum of 4 feet of chimney pipe sections required for outdoor installation Figure 1 Framing Dimensions Figure 2 Corner Installation FRAMING 1 Frame opening for fireplace using dimensions shown in Figures 1 and 2 Note When the fireplace is framed the header h...

Page 6: ...floor construction in front of fireplace Fab ricate a hearth extension using a material which meets the following specifications a layer of noncombustible inorganic material having a thermal conductivity of k 84 BTU IN FT2 HR F or less at 1 thick For example if material selected has a k factor of 0 25 such as glass fiber the following formula would apply 0 25 x 1 0 0 30 thickness required 0 84 The...

Page 7: ...2 18 24 36 and 48 snap lock double wall pipe segments planned for maximum adaptability to individual site requirements Actual lengths gained after fitting overlaps must be taken into consideration lineal gain and are given in lineal gain chart see Figure 6 Lineal gain is actual measurable length of a part after two or more parts are connected Figure 6 Lineal Gain Hemmed End 8 Stainless Inner Pipe ...

Page 8: ... a vertical chimney pipe supported ONLY by the fireplace must not exceed 20 feet Chimney heights above 20 feet must be supported USING ELBOW OFFSET 30E 12DMO 8DMR To clear overhead obstructions you may offset your chimney system using 30E 12DMO 8DMR 30 Offset return elbow A section or sections of chimney may be used between offsets and return elbow Transition pipe must be used after elbow offset i...

Page 9: ...2 3 4 1 1 1 38 1 2 75 1 2 1 1 3 39 1 4 76 3 4 1 1 1 1 41 1 2 80 1 2 1 1 2 1 42 1 4 81 3 4 1 1 1 1 44 1 2 85 3 4 1 1 1 1 1 45 1 4 87 1 1 1 1 47 1 2 91 1 1 2 1 48 1 4 92 1 4 1 1 2 49 3 4 94 3 4 1 1 2 1 1 52 98 3 4 1 1 1 4 53 1 2 101 1 4 1 1 1 2 54 1 4 102 3 4 1 1 1 1 55 3 4 105 1 4 1 1 3 1 56 1 2 1061 2 1 1 1 2 58 3 4 110 1 2 1 1 2 2 59 1 2 111 3 4 1 1 1 1 1 60 1 4 113 1 1 2 61 3 4 115 3 4 1 1 1 1 2...

Page 10: ...lete separation from one floor space to an other or attic space as required by most codes When double wall pipe passes through a framed opening into an attic space firestop must be placed into an attic floor as shown in Figure 11 Figure 10 Firestop Spacer with Living Space Above Ceiling Figure 11 Firestop Spacer with Attic Space Above Ceiling IMPORTANT NOTICE When penetrating a ceiling into an att...

Page 11: ...ipe and slide down until it is snug against open edge of flashing see Figure 14 Use SC1 for all round termina tions Apply waterproof caulk around perimeter of collar to provide a proper seal Figure 14 Storm Collar Chimney Pipe Waterproof Caulk Storm Collar Flashing Terminations Spark Arrestor Fireplace system must be terminated with listed round top or chase terminations In any case refer to insta...

Page 12: ...aised platform add height Provide sufficient gas line into fireplace chamber for fitting OPTIONAL GAS LINE INSTALLATION Figure 18 Typical Residential Installations VENTING INSTALLATION Continued connection see Figure 20 page 13 Note Secure incoming gas line to wood framing to provide rigidity for threaded end 4 Repack insulation around gas line and into sleeve opening Seal any gaps between gas lin...

Page 13: ...NING FIREPLACESEQUIPPEDWITHDOORS SHOULD BE OPERATED ONLY WITH DOORS FULLY OPEN OR DOORS FULLY CLOSED IF DOORS ARE LEFTPARTLYOPEN GASANDFLAMEMAYBEDRAWN OUT OF THE FIREPLACE OPENING CREATING RISKS OF BOTH FIRE AND SMOKE WARNING Discontinue use of the appliance imme diately if doors are damaged and contact a qualified installer for repair Only doors certified with the appliance shall be used WARNING ...

Page 14: ...ng guidelines instructions and warranty informa tion please refer to your homeowner s guide or contact your dealer Access Panel OPEN CLOSE Damper Handle Outside Air Kit Handle Keyway Slot Handle Retainer REPLACEMENT PARTS See Pages 16 to 18 for a complete replacement parts list Use only parts supplied from the manufacturer Normally all parts should be ordered through your IHP distributor or dealer...

Page 15: ...T 36 Section Hi Temp Double Wall Pipe Snap Lock F0885 48 8HT 48 Section Hi Temp Double Wall Pipe Snap Lock F0886 30E 8HT 30 Degree Hi Temp Offset and Return F0887 12S 8HT Hi Temp Chimney Support For Use With Chimney Heights In Excess of 30 F0888 RT 8HT Hi Temp Round Top with Mesh Screen F0889 RTT 8HT Hi Temp Round Top with Mesh Screen and Slip Sec tion F0890 RLT 8HT Hi Temp Round Top with Louvered...

Page 16: ...s com 127051 01_E 16 PARTS WOOD BURNING FIREPLACE MODELS 9 24 16 31 25 16 4 30 32 19 12 23 20 28 17 8 1 5 21 2 18 11 14 3 13 22 10 6 35 29 7 33 34 26 27 15 MODEL NO CATALOG NO Tuscan42P2 F0542 Tuscan42P3 F0543 ...

Page 17: ...Liner 1 11 See Page 18 Rear Refractory Brick Liner 1 12 See Page 18 Bottom Rear Refractory Brick Liner 1 13 See Page 18 Bottom Front Refractory Brick Liner 1 14 J3972 Firebox Support Leg 4 15 Damper Can Collar 1 16 J8013 Kit Screen Assembly 1 17 Firebox Top Assembly 1 18 J3980 Air Kit Door Assembly 1 19 Face Weldment 1 20 J4471 Air Deflector 1 21 Fireplace Top Insulation 1 22 Access Panel 1 23 J45...

Page 18: ... J4508 Bottom Front Refractory White Brick 1 PARTS WOOD BURNING FIREPLACE MODELS TUSCAN42P2 AND TUSCAN42P3 Rear Left Side Front Bottom Bottom Right Side MODEL NO CATALOG NO Tuscan42P2 F0542 Tuscan42P3 F0543 ACCESSORIES REFRACTORY STAIN KITS Use the refractory stain kits to give white refractory panels a new look Kit includes foam roller handle paint tray and one can of stain Available stain colors...

Page 19: ...ection Hi Temp Double Wall Pipe Snap Lock F0883 24 8HT 24 Section Hi Temp Double Wall Pipe Snap Lock F0884 36 8HT 36 Section Hi Temp Double Wall Pipe Snap Lock F0885 48 8HT 48 Section Hi Temp Double Wall Pipe Snap Lock 30 OFFSET AND RETURN F0900 30E 8DM 30 Degree Offset and Return F0886 30E 8HT 30 Degree Hi Temp Offset and Return F1908 30E 12DMO 8DMR 30 Elbow Set 12 to 8 Craftsman 42 F2199 30E 12H...

Page 20: ...on F0923 ETLO 8DM Square Top with Mesh and Slip Section MESH SQUARE TOP TERMINATION F0922 ETO 8DM Square Top with Mesh MESH SQUARE TOP TERMINATION WITH SLIP SECTION F0923 ETLO 8DM Square Top with Mesh and Slip Section STAINLESS STEEL HOOD Required when installing a vent free gas log in this fireplace F1053 HS42 42 Stainless Steel Hood w 4 Brow DRAIN PAN F1090 DP42 Drain Pan FIRESTOP THIMBLE F0911 ...

Page 21: ...ing the proper venting system for your installation American National Standards Institute ANSI NFPA 211 Standard for Chimneys Fireplaces Vents and Solid Fuel Burning Appli ances See Draft Section A chimney or vent shall be so designed and constructed to develop a flow sufficient to completely remove all flue and vent gases to the outside atmosphere The venting system shall satisfy the draft requir...

Page 22: ...The best location to install your appliance is determined by consid ering the location of windows doors and the traffic flow in the room where the appliance is located allowing space in front of the unit for the hearth extension and the mantel and taking into consideration the location of the hot air ducts some models outside air kit and chimney Ifpossible youshouldchoosealocationwherethechimneywi...

Page 23: ...or propane gas Fuel products with abnormal burning characteristics including but not limited to fuel such as driftwood coal or plywood and wood products using a binder may burn at excessive temperatures and may cause damage to the Product or may cause it to function improperly c damages caused by failing to provide proper maintenance and service in accordance with the instructions provided with th...

Page 24: ...01 Innovative Hearth Products reserves the right to make changes at any time without notice in design materials specifications prices and also to discontinue colors styles and products Consult your local distributor for fireplace code information Printed in U S A 2013 Innovative Hearth Products LLC P N 127051 01 Rev E 05 2017 1508 Elm Hill Pike Suite 108 Nashville TN 37210 ...

Reviews: