13
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Installation and Operation Instructions
900299-01, 05/2016
Innovative Hearth Products
Libra
™
Series Direct-Vent Gas Fireplaces
Gas Line
Center of gas line
is 3 in. (76 mm)
up from floor.
*41-1/2
(1054)
***48-1/2
(1232)
26-3/4
(679)
11-3/8
(267)
Dimension A
Secure Vent - 47-1/8 (1197)
Secure Flex - 47-3/4 (1213)
7
(178)
5-1/8
(130)
12-1/8
(308)
10-1/2
**22-3/4
(578)
LibraST
(See-Through)
VENT FRAMING -
TOP VENT WITH
ONE 90º ELBOW
VENT FRAMING -
REAR VENT WITH
NO ELBOWS
inches (millimeters)
7
(178)
5-1/8
(130)
12-1/8
(308)
6-1/4
(159)
A
Minimum Framing
Stud Size is 2x4
*This dimension can be reduced to 41 inches (1041 mm). This results in 0 in. (0 mm)
clearance between framing and unit framing spacers. (The 41-1/2 in. dimension permits
easier fireplace installation, if unit is installed after framing is erected.)
**This dimension based on 5/8” drywall.
For 1/2” drywall use 23”.
***Provide Additional Space For Side Vent
Seal Cap If Installing Against A Solid Wall
LibraPF
(Peninsula)
Gas Line
Center of gas line
is 3 in. (76 mm)
up from floor.
*41-1/2
(1054)
***43-5/8
(1108)
26-3/4
(679)
11-3/8
7
(178)
5-1/8
(130)
12-1/8
(308)
VENT FRAMING -
TOP VENT WITH
ONE 90º ELBOW
VENT FRAMING -
REAR VENT WITH
NO ELBOWS
inches (millimeters)
7
(178)
(130)
(308)
6-1/4
(159)
A
Minimum Framing
Stud Size is 2x4
(267)
(289)
**22-3/4
(578)
Dimension A
Secure Vent - 47-1/8 (1197)
Secure Flex - 47-3/4 (1213)
*This dimension can be reduced to 41 inches (1041 mm). This results in 0 in. (0 mm)
clearance between framing and unit framing spacers. (The 41-1/2 in. dimension permits
easier fireplace installation, if unit is installed after framing is erected.)
**This dimension based on 5/8” drywall.
For 1/2” drywall use 23”.
***Provide Additional Space For Side Vent
Seal Cap If Installing Against A Solid Wall
10-1/2
12-1/8
5-1/8
®
®
Gas Line
Center of gas line
is 3" (77 mm)
up from floor
* This dimension can be reduced to 41” (1042 mm). This results in 0” (0 mm) clearance between
framing and unit framing spacers. The 41-1/2” (1054 mm) dimension permits easier fireplace
installation, if unit is installed after framing is erected.
Optional Gas Line Location
Center of gas line is 3" (77 mm)
up from floor
* This dimension can be reduced to 41” (1042 mm). This results in 0” (0 mm) clearance
between framing and unit framing spacers. The 41-1/2” (1054 mm) dimension permits easier
fireplace installation, if unit is installed after framing is erected.
Gas Line
Center of gas line
is 3" (77 mm)
up from floor
Figure 14
Figure 13
Figure 15
Figure 16
FIREPLACE FRAMING SPECIFICATIONS
LibraST
(See Through)
LibraCL (Corner Left)
LibraPF
(Peninsula)
LibraCR (Corner Right)