Manual BA 662
Technical changes reserved. 09/2016
Page 7 of 10
A.S.T. - Angewandte System Technik GmbH, Mess- und Regeltechnik
0 … +10V
0 … + 5V
-10 … +10V
-5 … + 5V
0 … 20mA
0 … 24mA
4 … 24mA
4.4. Zero alingment
>0% + < and >0% - < simultaneously (2s):
Setting of the present input signal at the output to zero point (zero-adjustment/ zero-alignment)
By individually pressing the keys >0% +< or >0% -< respectively, an individual fine adjustment
of the output signal / the zero point is possible.
NOTE!
Zero-values are saved permanently 7 seconds after last push button action.
During saving LED blinks red for a short time.
4.5. Filter
Through a low-pass filter, the output signal can be set in 10 stages, from 0.8 to 2000Hz.
Filter (Hz)
0,8
2,4
8,3
25
67
156 385 625 1315 2000
Internal Sample rate (Hz)
6
12
25
50
100 200 400 800 1600 3200
4.6. Signal output
DIP-switch explanation:
DIP-switch function:
ATTENTION!
In case of exceedance of the input signal of >-120%, the analogue
output is set to the maximum positive initial value.
In case the input signal lies in the range between -120% and 0%, the minimum
analogue signal is released at the unipolar voltage output and the current output
respectively (
see too 4.7
).
Input
output bipolar (U)
120%
-120%
Input
Sensor mV/V
output unipolar (U/I)
-120%
120%
Graph 1
Output signal in case of error (bipolar)
Output signal -5…5V, -10…10V
Graph 2
Output signal in case of error (unipolar)
Output signal 0…5/10V, 0/4…20/24mA
3 2 1
- OFF -