Manual BA 662

 

 

Page 2 of 10 

Technical changes reserved. 09/2016 

 

A.S.T. - Angewandte System Technik GmbH, Mess- und Regeltechnik 

1.  Safety precautions 

In this operating manual, the installation, putting into operation and the operation itself of the 
Strain Gauge Bridge Amplifier BA 662 is described. It is assumed that all measures are taken 
by  qualified  staff  only  who  have  adequate  knowledge  in  the  fields  of  measuring  and  control 
engineering. 
 

 

ATTENTION! 

Any non-compliance with these safety precautions may result in 

severe damage to property and health.

 

 

1.1.  Field of application 

The Strain Gauge Bridge Amplifier BA 662 has been designed to the purpose of amplifying the 
output  signals  of  sensors  with  metal-foil  strain  gauges,  preferably  force  transducers  and 
transform  them  into  standard  signals.  Any  other  application  is  regarded  contrary  to  the 
intended purpose. The manufacturer does not accept any liability for damages resulting from 
such inappropriate usage. In this case it is the user alone who has to bear the risk. 
Type  BA 662  must  not  be  used  as  the  sole  means  to  prevent  dangerous  conditions  of 
machines  and  plants.  All  machines  and  plants  must  be  constructed  in  such  a  way  (e.g.  by 
using mechanical stops, limit switches) that a condition of failure does not result in a situation 
of severe danger. 
It  must  be  made  sure  that  any  erroneous  setting  or  malfunction  of  the  unit  or  its  breakdown 
cannot cause damage or be a risk to the operating staff or other persons. 
 

1.2.  Installation 

The  unit  must  be  installed  and  connected  in  compliance  with  the  current  DIN-  and  VDE-
standards. Supply cables and signal lines shall be installed so that interference signals such as 
electrical interference do not have any adverse effects on the function of the equipment. 
 

1.3.  Maintenance  

The  device  does  not  contain  any  components  that  require  maintenance.  Repairs  shall  be 
carried out by the manufacturer only. 

2.  Function 

The Strain Gauge Bridge Amplifier BA 662 is a digital amplifier for the low-drift amplification of 
the  output  signals  of  sensors  with  metal-foil  strain  gauges,  preferably  force  transducers  to 
supply a standard signal of (-10/0...10) VDC or (0/4...20) mA. 
An internal voltage source provides the stabilized feeding voltage for the sensor. The power is 
supplied  by  an  unstabilized  source  of  (9...36)  VDC.  The  Strain  Gauge  Bridge  Amplifier  is 
delivered in a case for standard rails in accordance with DIN EN 50022-35.  
The BA 662 is delivered with a factory setting for an input signal of 2mV/V and a corresponding 
output  signal  of  ±  10V  or  20mA.  The  other  input  signal  ranges  0.1mV/V  to  7mV/V  can  be 
generated internally from the 2mV/V factory adjustments. The different settings of the factory 
adjustments (zero point and gain) can be changed by the user through keys. 
By  an  optically  separated  input,  the  zero-setting  can  be  carried  out  by  means  of  a  superior 
control and through the trigger input. The overload limit is not affected by such a zeroing, which 
means that 100 % of the end-value adjustment of the sensor remains as end value. An existing 
preload by a container can thus be set zero. 

Summary of Contents for BA 662

Page 1: ...nance 2 2 Function 2 3 Specifications 3 3 1 General technical data 3 3 2 Circuit diagram 4 3 3 Dimensions 4 3 4 Connections 5 3 5 How to connect signal output 5 3 6 Trigger input 5 4 Operation 6 4 1 Overview operating elements BA662 IP20 6 4 2 How to operate the keys 6 4 3 Amplification 6 4 4 Zero alingment 7 4 5 Filter 7 4 6 Signal output 7 4 7 LED Status 8 4 8 Restart 8 4 9 Factory setting RESET...

Page 2: ...rating staff or other persons 1 2 Installation The unit must be installed and connected in compliance with the current DIN and VDE standards Supply cables and signal lines shall be installed so that interference signals such as electrical interference do not have any adverse effects on the function of the equipment 1 3 Maintenance The device does not contain any components that require maintenance...

Page 3: ...Current Output Voltage Output Load resistance mA V Ω 0 4 20 0 24 500 10 5 0 5 10 1000 Measurement Characteristics Conversion rate Hz 6 3200 Resolution of the A D Converter Bit 24 Filter Hz 0 8 2000 Error at S 2mV V Nonlinearity Noise at measurement rate Input sensitivity for 1 LSB Zero drift FSR FSR nV 10K 0 0025 0 002 0 8Hz 0 009 2000Hz 150 0 01 Power Supply Input range Power consumption without ...

Page 4: ...nfig DAC AG VOut I Out 9 36VDC 0V 1 Stab Filter 2 Stab 2 Stab Shi EMC Filter Output Sensor T 24VDC T 0V USB ASTAS Configuration DAC Filter 3 3 Dimensions AG Si Si 24V Ex Ex VOUT IOUT 0V Se Se Tr NC NC SHI Tr Output 0 10V 0 5V 10 10V 5 5V 0 20mA 0 24mA 4 20mA Filter Hz 0 8 156 8 3 2000 1315 625 385 67 25 2 4 99 22 5 114 5 6 Wire 4 Wire 100 0 mV V Status BA 662 0 1 2 0 0 5 0 25 1 5 1 0 3 0 4 0 5 0 7...

Page 5: ...g upon the setting of the slide switches see 4 6 NOTE Either the current output or the voltage output can be used not both at the same time TIP o form the sum current outputs of several BA662 can be connected in parallel In this case 12V should not be exceeded at the standard output and the maximum load load resistance be 12V IOut Voltage outputs must not be connected in parallel 3 6 Trigger input...

Page 6: ...e the keys Keys individually short Setting of the signal output Keys individually long 2s Fast setting of the signal output 4 3 Amplification Switch position 0 1 2 3 4 5 6 7 8 9 Measuring range mV V 0 1 0 25 0 5 1 0 1 5 2 0 3 0 4 0 5 0 7 0 100 and 100 simultaneously 2s Adjustment of the present input signal currently applied force to100 of the output signal end value adjustment By individually pus...

Page 7: ...ass filter the output signal can be set in 10 stages from 0 8 to 2000Hz Filter Hz 0 8 2 4 8 3 25 67 156 385 625 1315 2000 Internal Sample rate Hz 6 12 25 50 100 200 400 800 1600 3200 4 6 Signal output DIP switch explanation DIP switch function ATTENTION In case of exceedance of the input signal of 120 the analogue output is set to the maximum positive initial value In case the input signal lies in...

Page 8: ...ry setting RESET For all ten sensitivity settings measuring ranges see 4 1 sensitivity in mV V of the sensor factory settings are stored in the amplifier Individual adjustments of the amplification see 4 3 or of the zero point see 4 4 carried out later by the user do only influence the active measuring range that has just been set When simultaneously pushing the two keys 100 and 0 for 2s all zero ...

Page 9: ...Manual BA 662 Technical changes reserved 09 2016 Page 9 of 10 A S T Angewandte System Technik GmbH Mess und Regeltechnik 6 EC Declaration of Conformity ...

Page 10: ...Manual BA 662 Page 10 of 10 Technical changes reserved 09 2016 A S T Angewandte System Technik GmbH Mess und Regeltechnik ...