background image

 
Copyright © 2010, 2014 Yale Security Inc., an ASSA ABLOY Group company. All rights reserved. 
Reproduction in whole or in part without the express written permission of Yale Security Inc. is prohibited. 

80-9372-0100-015 (02-14)

ASSA ABLOY

RI X SON

®

1

Requirements:

Units are handed. Hand of unit and hand of door must be the same.

All dimensions shown in inches (mm).

Door must be hung on ball bearing butt hinges or 3/4" (19) offset pivots.

Door thickness must be 1-3/4" (44) to 2-1/4" (64).

Door must swing freely through the entire opening and closing cycle before beginning the installation procedure.

Frame face must be a minimum of 2" (51).

Ceiling clearance must be a minimum of 3 -1/2" (89) for push side application or 4" (102) for pull side application. See pages 
2 and 7 for templates.

Power input to unit must be of the same voltage as that stated on the unit.

Unit to be mounted on interior of building in dry environment, maximum humidity of 95%.

See NFPA70 for wiring requirements and NFPA72 for alarm system requirements.

Pull Side Applications with Slide Track
(4 Pull, 6 Pull)

(see page 7 for template)

Push Side Applications with Double Lever Arms
(4 Push, 6 Push)

(see page 2 for template)

Item No. Description

1           Track (Pull Side)

2           Cover
3           Track Arm (Pull Side)
4           Double Lever Arm (Push Side)

• Allen wrench set (inch)
• Flat blade screwdriver (potentiometer & 
terminal size)
• Screwdriver (Phillips size 2)

      • Tape ruler

• Power drill 
• Center punch
• Wire stripper

Tools required:

Use screw pack and hardware provided to mount operator. 

3

1

2

4

Table of Contents:

Push  Side Template....................2
Push  Side  Installation..............2-4
Closer  Adjustments.....................5
Hold Open Position Adj...............6
Pull  Side  Template......................7
Pull Side Installation.................7-9
Closer  Adjustments...................10
Hold Open Position Adj.............11
Non-Detectored  Electrical.........12
Detectored  Electrical.................13
RF Unit Electrical.................14-15
Troubleshooting.........................15
General  Information..................16

ASSA ABLOY

RI X SON

®

Smok-Chek® VI 

Installation and Instruction Manual

ASSA ABLO

Y

RIX SO

N

®

ASSA ABL

OY

RIX S

ON

®

Summary of Contents for Rixson Smok-Chek VI

Page 1: ...rior of building in dry environment maximum humidity of 95 See NFPA70 for wiring requirements and NFPA72 for alarm system requirements Pull Side Applications with Slide Track 4 Pull 6 Pull see page 7...

Page 2: ...ge Of Door DOOR OPENING ANGLE Dim A Inches mm To 100 100 to 180 5 7 8 3 1 8 149 2 79 4 Hinge or Pivot Drill 7 Tap 1 4 20 UNC 19 3 4 1 3 4 44 5 C 4 101 6 11 1 4 285 8 501 7 For Concealed Wiring Only 7...

Page 3: ...g closer body by key hole slots b and slide closer toward hinge to capture screw heads c Warning Do not allow pedestrian traffic through opening until all mounting screws are tightened Closer Mounting...

Page 4: ...er Spring Adjustment 3 8 11 16 Wrench Closing Force Weaker Stronger Slowly increase closer power until door closes consistently A closer set to the ADA required 5 lbs opening force may not be strong e...

Page 5: ...remove valves from closer Hydraulic oil will escape 1 8 Hex Key 1 8 Hex Key w o e l r S F r aste w o e l r S F r aste Weaker Stronger Closing Speed Controls Valve S Controls Sweep Range from full ope...

Page 6: ...d units detectored units cannot be turned off at the closer See previous step Open door to desired hold open angle Loosen cam screw and rotate cam until switch closes and door holds open Rotate cam un...

Page 7: ...oor shown left hand opposite All dimensions shown in inches mm Install two screws in the key slot locations leaving 1 8 gap between screw head and frame as shown a a C 1 8 1 Track Mount Unit 6 152 4 1...

Page 8: ...8 wrench provided Mount closer arm to pinion square as shown Use main arm to rotate pinion until flat is visible RE INSTALL HERE LEFT HAND RIGHT HAND Attach with provided screw and washer Tighten arm...

Page 9: ...r than 125 spring cushion stop cannot be used and an auxiliary stop by others is required Mount Track 3 7 Connect Arm to Track 3 8 Open door to maximum desired swing minus 5 and hold Slide spring cush...

Page 10: ...ves from closer Hydraulic oil will escape 1 8 Hex Key w o e l r S F r aste Weaker Stronger Closing Speed Controls Valve S Controls Sweep Range from full open to 5 Valve L Controls Latch Range from 5 t...

Page 11: ...en position SHO switch in open position Closer not in hold open SHO switch in closed position Closer in hold open Un used pin Setting Hold Open Angle Make all required electrical connections and turn...

Page 12: ...strations below NON DETECTORED ELECTRICAL CONNECTIONS Surface mount power input Remove appropriate shaded area from cover for surface wired installations only Repaint cut edges as necessary to prevent...

Page 13: ...w SMOKE DETECTOR ELECTRICAL CONNECTIONS 120V AC INPUT Surface mount power input Remove appropriate shaded area from cover for surface wired installations only Repaint cut edges as necessary to prevent...

Page 14: ...block or power supply using illustrations below RF REMOTE RECEIVER UNITS ELECTRICAL CONNECTIONS 120V AC INPUT Surface mount power input Remove appropriate shaded area from cover for surface wired ins...

Page 15: ...tton on the receiver depending on the activation requirements If delay learn is selected adjust potentiometer to counterclockwise limit 0 second delay After learn cycle is complete adjust potentiomete...

Page 16: ...tch 9 32 7 mm thru 3 8 9 5 mm dia x 3 8 9 5 mm deep on door opposite to closer Standard Optional Through bolts and grommet nuts All Preparation for Fasteners Door or Frame Fasteners Drill Sizes 1 4 20...