11
EN
Installation
Bus controller installation
The
TSB Controller II
is intended for installation in a suitable electrical distributor.
It is mounted on top-hat rails according to DIN EN 60715 TH35. The wiring takes
place via screw-type terminals.
The installation location of the
TSB Controller II
distributor must meet the follow-
ing conditions:
· It must be on the inside of the building.
· It must not be exposed to any unusual environmental conditions, such as ag-
gressive vapours or high humidity.
· The
TSB Controller II
should be easily accessible in a protected area and not be
exposed to direct sunlight.
· When mounting the
TSB Controller II
on the wall, take care not to damage any
wiring or pipes inside the wall itself. The module rack for the
TSB Controller II
and
fastening screws must not come into contact with conductive elements in the
building’s structure.
Power supply
The
TSB Controller II
must be powered by an external power supply.
The power supply unit must comply with the specifications described in chapter
“Technical data”, page 22.
Installation
location
external power
supply