Fig. 6.8
Fig. 6.9
V
alve cove
6.4 Instructions for Connecting Piping to Outdoor Unit
Caution
Use spanner to grip main body of valve
Torque from tightening the flare nut can snap off other parts of valve.
1. Unscrew the cover from the packed valve on the side of the outdoor unit. (See Fig. 6.9)
2. Remove protective caps from ends of valves.
3. Align flared pipe end with each valve, and tighten the flare nut as tightly as possible by hand
.
4. Using a spanner, grip the body of the valve. Do not grip the nut that seals the service valve. (See Fig. 5.10)
5. While firmly gripping the body of the valve, use a torque wrench to tighten the flare nut according to the
correct torque values.
6. Loosen the flaring nut slightly, then tighten again.
7. Repeat Steps 3 to 6 for the remaining pipe.
6. Refrigerant Piping Connection