Note
:
The size of the power supply cable, signal cable, fuse, and switch needed is determined by the maximum
current of the unit. The maximum current is indicated on the nameplate located on the side panel of the unit.
Refer to this nameplate to choose the right cable, fuse, or switch.
The air conditioner’s circuit board (PCB) is designed with a fuse to provide overcurrent protection. The
specifications of the fuse are printed on the circuit board, such as: T3.15A/250VAC, T5A/250VAC, etc.
Fig. 4.10
Caution
W
arning
1. Prepare the cable for connection:
a.Using wire strippers, strip the rubber jacket from both ends of signal cable to reveal about 40mm (1.57in)
of the wires inside.
b.Strip the insulation from the ends of the wires.
c. Using wire crimper, crimp u-type lugs on the ends of the wires.
Note:While crimping wires, make sure you clearly distinguish the Live (“L”) Wire from other wires.
2. Open front panel of the indoor unit.
3. Using a screwdriver, open the wire box cover on the right side of the unit. This will reveal the terminal block.
4. Unscrew the cable clamp below the terminal block and place it to the side.
5. Facing the back of the unit, remove the plastic panel on the bottom left-hand side.
6. Feed the signal wire through this slot, from the back of the unit to the front.
7. Facing the front of the unit, match the wire colors with the labels on the terminal block, connect the u-lug and
and firmly screw each wire to its corresponding terminal.
8. After checking to make sure every connection is secure, use the cable clamp to fasten the signal cable to the
unit. Screw the cable clamp down tightly.
9. Replace the wire cover on the front of the unit, and the plastic panel on the back.
Note: The wiring connection process may differ slightly between units.
All wiring must performed strictly in accordaance with the wiring diagram located on the inside of the indoor
unit’s
wire cover.
Do not mix up live and null wires!
This is dangerous, and can cause the air conditioning unit to malfuncation.
16
4. Indoor Unit Installation
Terminal block
Terminal block cover
Screw
Cable clamp
Wire cover