Outdoor Unit
Outdoor Unit Wiring Diagram
is located on the inside of the
wire cover on the outdoor unit.
Cover
W
arning
All wiring must performed strictly in accordaance with the wiring diagram located on the inside of the outdoor
unit’s
wire cover.
1. Prepare the cable for connection:
Use the right cable
Indoor Power Cable (if applicable): H05VV-F or H05V2V2-F
Outdoor Power Cable: H07RN-F
Signal Cable: H07RN-F
W
arning
Before performing any electrical or wiring work, turn off the main power to the system.
Do not let wires touch or rest against refrigerant tubing, the compressor, or any moving parts with the unit.
If the unit has an auxiliary electric heater, it must be installed at least 1 meter (40in) away from any
combustible materials.
a.Using wire strippers, strip the rubber jacket from both ends of signal cable to reveal about 40mm (1.57in)
of the wires inside.
b.Strip the insulation from the ends of the wires.
c. Using wire crimper, crimp u-type lugs on the ends of the wires.
Note:While crimping wires, make sure you clearly distinguish the Live (“L”) Wire from other wires.
2. Unscrew the electrical wiring cover and
r
emove it.
3. Unscrew the cable clamp below the terminal block and place it to the side.
4. Match the wire colors/labels with the labels on the terminal block, and firmly screw the u-lug of each wire to its
corresponding terminal.
5. After checking to make sure every connection is secure, loop the wires around to prevent rain water from
flowing into the terminal.
6. Using the cable clamp, fasten the cable to the unit. Screw the cable clamp down tightly.
7. Insulate unused wires with PVC electrical tape.
Arrange them so that they do not touch any electrical or metal parts.
8. Replace the wire cover on the side of the unit, and screw it in place.
5. Outdoor Unit Installation
22
> 16 and ≤ 25
2.5
> 25 and ≤ 32
4
> 32 and ≤ 40
6
Minimum Cross-Sectional Area of Power and Signal Cables
Rated Current of Appliance (A)
Nominal Cross-Sectional Area (mm²)
> 3 and ≤ 6
0.75
1
1.5
> 6 and ≤ 10
> 10 and ≤ 16