65
107750-01 - 9/17
VII. Venting
I. Assembly of Stainless Steel Vent Systems
1. This boiler has been listed for use with DuraVent FasNSeal Flex Stainless Steel vent systems to be provided by the
installer.
WARNING
Asphyxiation Hazard. Follow these instructions and the installation instructions included by the
original stainless steel venting component manufacturer, DuraVent. Failure to do so could cause
products of combustion to enter the building, resulting in severe property damage, personal injury
or death. Where a conflict arises between DuraVent instructions and these instructions, the more
restrictive instructions shall govern.
Do not mix components from listed manufacturers.
Examine all components from listed manufacturers.
All condensate that forms in the vent must be able to drain back to the boiler.
2. The vent adaptor has three different diameters. The lower diameter accepts 4" Stainless steel (Figure 7.26).
A locking band clamp in the adaptor prevents the vent pipe from coming out of the adaptor once it is installed and
tightened. Lubricate the upper gaskets in the vent adaptor with water and insert the first piece of 4" stainless into the
adaptor until it bottoms out. Tighten locking band clamp to secure vent pipe.
3. Installation of Air Intake System - Start assembly of the PVC air intake system at the boiler. Assembly of the air intake
system is done in the same manner as the vent system expect as follows:
a. Drill a 7/32" clearance hole into the front side of the air intake adaptor. Insert the first piece of PVC air intake pipe into the
air intake connection and drill a 1/8" tap hole into the PVC which lines up with the 7/32" clearance hole and secure them
together with a #10 x 1" sheet metal screw. Seal the joint between the intake pipe and the adaptor with RTV.
b. All intake piping may be PVC.
c. There is a 0" minimum clearance between the air intake piping and all types of construction.
d. To the extent possible, pitch horizontal air intake piping towards the outside.
WARNING
Asphyxiation Hazard. Vent systems made by DuraVent rely on gaskets for proper sealing. When these vent
systems are used, take the following precautions:
• Make sure that gasket is in position and undamaged in the female end of the pipe.
• Make sure that both male and female pipes are free of damage prior to assembly.
• Only cut vent pipe as permitted by the vent manufacturer in accordance with their instructions.
When pipe is cut, the cut end must be square and carefully de-burred prior to assembly.
4. Installation using DuraVent FasNSeal Flex (Vent Option 39) - Refer to manufacturer's instructions for assembly of all
flex components including the chimney cap and adaptor to rigid pipe at base of masonry chimney. In addition, observe
the following requirements:
a. Refer to the appropriate Vent Option in Table 7.21 for a list of the principle flex components required. Rigid vent pipe by
the same manufacturer will also be required for the run from the boiler to the base of the chimney.
b. Masonry chimneys cannot be used for an air chase.
c. Flexible stainless steel vent shall be installed in an UNUSED masonry chimney and supplying combustion air through a
separate wall or roof combustion air terminal. The unused chimney flue must be structurally sound and in good repair. A
chimney is considered UNUSED when it is not being used for an appliance venting, the flexible stainless vent installation
is permitted through an adjacent, unused flue providing a local authority having jurisdiction approves such installation.
(Figure 7.25b)
NOTICE
The venting system must be free to expand and contract and supported in accordance with the installation
instructions included by the original stainless steel venting component manufacturer.
I. Assembly of Stainless Steel Vent Systems
Summary of Contents for ASPN-320
Page 88: ...88 107750 01 9 17 Figure 10 4 Proper Installation of Header Sensor X Wiring continued ...
Page 89: ...89 107750 01 9 17 Figure 10 5 Internal Wiring Ladder Diagram X Wiring continued ...
Page 90: ...90 107750 01 9 17 X Wiring continued CONDENSATE FLOAT SWITCH ...
Page 91: ...91 107750 01 9 17 X Wiring continued Figure 10 6 Internal Wiring Connections Diagram ...
Page 100: ...100 107750 01 9 17 Operating Instructions XI Start Up and Checkout continued ...
Page 145: ...145 107750 01 9 17 XV Service Parts continued ...
Page 147: ...147 107750 01 9 17 XV Service Parts continued All Models ...
Page 149: ...149 107750 01 9 17 XV Service Parts continued All Models ...
Page 151: ...151 107750 01 9 17 XV Service Parts continued All models ...
Page 157: ...157 107750 01 9 17 ...
Page 158: ...158 107750 01 9 17 ...
Page 159: ...159 107750 01 9 17 ...