background image

 

       American Stainless Pumps, Inc. 

www.aspumps.com 

2

Safety Instructions (continued…) 

1.  Always disconnect and lockout the electrical power source before attempting any connection, maintenance or repairs. 

Failure to do so can cause electrical shocks, burns and death. 

2.  Install ground and wire motors in accordance with all local and national electrical codes. 
3.  Install an all leg disconnect switch near the motor for quick access. 
4.  The  electrical  supply  must  match  the  motor  nameplate  specifications  and  the  motor  must  be  wired  per  the  wiring 

diagram on the motor to match the selected voltage. 

Incorrect wiring can cause fire and motor damage and will 

void the warranty. 

5.  Most single-phase motors and some three phase motors will have automatic thermal protection switches wired in the 

motor. These switches will open and stop the motor if  the motor overheats. As the motor cools, these switches will 
close and start the motor automatically and unexpectedly. 

6.  Motors which do not have thermal overloads must have a properly sized contacts or magnetic starters and overload 

switches (or fuses) in the starter panel. Three phase motors require all leg protection. 

7.  Use  only  stranded copper wire  to  motor  and  ground.  Wire  size  must  limit  the maximum  voltage  drop  to 10%  of  the 

motor nameplate voltage at the motor terminals. 

8.  Three  phase  motors  (and  some  single  phase  motors)  can  rotate  in  either  direction.  The  pump  will  operate  properly 

only in one direction (clockwise when looking from the motor end, counterclockwise when viewed from the pump end). 

Operating  the  pump  in  the  reverse  rotation  may  damage  or  destroy  the  pump  and  motor,  and  voids  the 
warranty

. See section below titled, Rotation. 

Installation

Units may be installed horizontally, at an angle or vertically with the motor on top. 

Do not mount the motor below 

the pump as leakage from the pump will damage the motor and can cause a shock, burns or 
death.

 

 

Locate the pump as near to the liquid source as possible. The pump must be primed with little or no air in the case to 
begin  operation.  Ideally,  the  pump  should  be  located  below  the  liquid  level  when  starting.  This  pump  is  not  self-
priming.

 

 

Protect the pump and motor from freezing. The pump will sustain significant damage if allowed to freeze. 

 

 

Allow adequate space around the unit for service and ventilation. 

 

 

Units mounted horizontally should be located on a flat, rigid surface. 

 

 

Unit may be free standing, but some vibrations may occur. If attached to a foundation, tighten hold down bolts before 
connecting the piping. 

Piping

 

 

All piping must be independently supported. No piping loads may be carried by the pump. 

 

 

Piping should be the same size or larger than the pump connections. 

 

 

Proper  Piping  to  the  suction  is  critical  for  proper  pump  operation.  Suction  pipe  should  be  short  and  direct,  with  a 
minimum of fittings and turns. 

 

 

Suction pipe must be designed to avoid potential air pockets. All pipe connections must be airtight. 

 

 

If suction pipe is larger than the pump’s suction port, an eccentric reducer should be used with the straight side on top 
to avoid creating an air pocket. 

 

 

If suction of pump is above the liquid level source, a foot valve or other isolation valve will be needed to maintain the 
prime of the pump. A continuous stream of liquid must be made available for the pump suction to hold its prime. 

 

 

Be sure that the source liquid level is sufficient to prevent vortices from drawing air into the pump. 

 

 

Install suction and discharge valves for isolating the pump during maintenance and inspection. 

 

 

Do not use any suction valve for throttling the pump. This may cause a loss of prime, and damage to the pump that is 
not  covered  by  warranty.  Flow  regulating  using  throttling  valves  should  only  be  done  on  the  discharge  side  of  the 
pump. 

Summary of Contents for SSP

Page 1: ... vs Ceramic faces with Buna N elastomers mechanical seal A maximum temperature limit of 250 deg F is possible with Viton elastomers The motor is limited to 20 starts per hour evenly distributed Minimum flows are 5 of the best efficiency operating point These pumps are not designed for use with hazardous liquids or gasses Notice Upon receipt of this equipment inspect the carton and the equipment fo...

Page 2: ... on top Do not mount the motor below the pump as leakage from the pump will damage the motor and can cause a shock burns or death Locate the pump as near to the liquid source as possible The pump must be primed with little or no air in the case to begin operation Ideally the pump should be located below the liquid level when starting This pump is not self priming Protect the pump and motor from fr...

Page 3: ...e the pump beyond the flow rates shown on published curves Noisy pumps or the sounds of pumping rocks may be signs of cavitation or operation beyond the pumps capacity Check pump and motor for vibration Vibration may be a sign of pipe strain insufficient mounting or operation beyond the pumps capacity The pump models SSP SSPC are not designed for handling large amounts of solids For the model SSP ...

Page 4: ...n while turning the impeller DO NOT apply any heat to the components If you are unable to hold the shaft in this manner remove the rear motor housing and grip the motor shaft with vise grips or other similar device do not hold shaft where bearings will mount 8 Model SSP Only There should be several spacing washers behind the impeller These spacers locate the open impeller vanes close to the case f...

Page 5: ...kness of impeller spacer washers onto the threaded portion of the shaft If you are not changing the impeller or the motor use the same batch of spacer washers you removed when disassembling the pump See the section on Setting Impeller Clearance for procedures if you are changing the impeller to case setting or are building a new pump 8 Thread the impeller onto the pump shaft and tighten into place...

Page 6: ... have any spacers when the customer elects to accept reduced performance in return for ease of assembly Use the following impeller shimming method when building a new pump 1 Place the pump as assembled through step 4 of the Assembly section above on the workbench positioned vertically 2 Place 0 050 shims onto the motor shaft two 0 015 shims and two 0 010 shims 3 Thread the impeller onto the shaft ...

Page 7: ...Mechanical Seal Type 16 Car Cer Buna N 304SS Other materials SilCar Viton EPR 400 Seal Plate 304 SS 500 Casing O Ring Buna N Viton EPR 510 Impeller O Ring Enclosed Imp Only Buna N Viton EPR 600 Motor Adapter Plate 304 SS 720 Impeller Shims Washers 0 010 0 015 thick 304 SS 7CS Case Screw 20 x 304 SS 7DP Casing Drain Plug 1 8 NPT 304 SS 7MB Motor Bolt 3 8 16 x 304 SS 7SC Impeller Washer Screw 3 phas...

Page 8: ...ld FOB The Factory Freight charges for returning and reshipping products are the buyer s responsibility regardless of warranty status There are no other warranties expressed or implied except for the warranties given here This warranty may not be modified verbally by any employee or agent of ASP Returns All products returned to ASP for warranty evaluation must be authorized in advance by the issua...

Reviews: