Hysteresis
Hysteresis
High Limit
Low Limit
Position
CAM Status
activ 1
inactive 0
© by ASM GmbH
MAN-PRDS-E-17 29
www.asm-sensor.com / USA: www.asmsensors.com
View to sensor connector
Signal wiring /
connection
Signal name
Connector pin
Wire color
Shield
1
Braid
Exci
2
White
GND
3
Brown
CAN-H
4
Blue
CAN-L
5
Black
CAN bus
wiring
CAM
function
Connect the device by a T-connector to the CAN trunk line. Total length of
stubs should be minimized. Do not use single stub lines longer than 0.5 m.
Connect terminating resistors 120 Ohm at both ends of the trunk line.
Terminating
resistor
T-Connector
CAN bus cable
Sensor
POSIROT
®
– PRDS
Output CANopen