VIPET - Hardware Installation and Maintenance Guide
U-0582-0512.doc – Issue: 05 complete, approved
Page 13 of 24
Figure 3
VIPET-PSU-MAINS Connection Diagram
The VIPET-MAINS-FILTER includes:
1 x FILTER
1 x WSI6 FUSE TERMINAL WITH 1 x T1A FUSE
2 x EW35 TERMINALS
DIN RAIL
L
N
E
L
N
E
LINE
LOAD
HARMONISED COLOURS:
L = LIVE = BROWN
N = NEUTRAL = BLUE
E = EARTH (SYSTEM ELECTRICAL SAFETY EARTH) = GREEN/YELLOW
FILTER
FUSE T
E
RMINAL
TO VIPET(S)
OR
TO UPS UNIT(S) WHICH POWERS THE VIPET(S)
FUSE TERMINAL
WSI6
FUSE: T1A - T5A (1A PER VIPET)
Filter output can only be used to power VIPET(s):
y
Directly connected, or
y
Connected via UPS. UPS to only power VIPET(s).
Number of VIPETs limited by the fuse in FUSE TERMINAL. Allow 1A per VIPET.
Maximum of 5 VIPETs to be powered through any one filter, whether they are connected directly to the filter,
through number of UPS units, or combination of the two.
!
!
LINE
LOAD
y
The VIPET-MAINS-FILTER is to be mounted on a DIN rail within the main equipment rack.
y
The FUSE TERMINAL is to be mounted as close to the VIPET-MAINS-FILTER as possible.
y
The position is dependent on specific design, cable entry direction etc.
y
Normal standard mains cabling installation. Current rating to suit particular installation.
y
Cable ends to be fitted with suitable bootlace ferrules.
!
!
EARTH BAR
MAINS 'N'
MAINS 'L'
EW
35 (
*)
EW
35 (
*)
(*) EW35 TERMINAL TO FIX
FILTER IN PLACE
FI
L
T
E
R