background image

230V

40-65Hz

140V-300V

Yes

3 Pin 10A, Indian Plug, 1.2 mt wire

230V +10%~-15%

Follows Input

230V ±10%

50 Hz ±1%

Modified Sinewave

0.6

>80%

3 output sockets

UPS output cutoff immediately

110% for 1 min

130% for 3 sec

4-8 ms

12V

7AH, SMF

Auto Discharge Protection

6 hrs (to 90% full capacity)

approx.  10-15 mins

LED steady

LED blink

Slow beeping sound (about 0.47 Hz)

Rapid beeping sound (about 1.8 Hz)

Continuos beeping sound

0-40°C, 0-95% humidity non condensing, 3500 meter max.

<40DbA (1 meter from surface)

15,000 meter max. elevation

4.2 Kgs.

101 x 279 x 142

IND600

1 PC Load (max 600VA)

Capacity
Voltage
Frequency
AVR
Generator Compatible
Connection
Voltage on mains
Frequency on mains
Voltage on Battery
Freq on Battery
Waveform
Power Factor Lagging
Efficiency
Sockets
O/p Short cct
O/p overload shutdown

Mains to Inverter
DC Bus
Internal Battery
Proctection
Typical Recharging Time
Backup time on PC 
with LCD monitor
Power ON
Inverter ON
Battery Backup
Battery Low
Overload
Ambient Operation
Audible Noise
Storage Condition
Weight (Kgs.)
Dimension - WxDxH (mm)

Features

!

Line interactive design

!

Boost and buck AVR (Auto voltage 
regulation)

!

Cold start function (DC power on)

!

Advanced battery management 
(ABM technology)

!

Battery charging in UPS OFF Mode

!

Microprocessor controlled

Specifications - 

IND600

Model

Input

Output

Protection 

Transfer Time
Battery

Indications

Alarm

Environment

Physical

ASIA POWERCOM PVT. LTD.

H.O.:

 401, 402 4th Floor,Arya Arcade CHS, Station Road, Vikhroli West , Mumbai - 400083.

[email protected][email protected] • www.asiapowercom.com

Error/Problem

No LED
display
on the
front panel.

Alarm buzzer
beeps
continuously
when AC
supply is
 normal.

When Power
failure, backup
 time is
shortened.

Possible cause

Battery defect.

Power switch is
not pressed
.

Overload of
the UPS.

Overload of
the UPS.

Battery voltage 
is too low.

Battery defect
due to high
temp. operation
environment, or
improper
operation
of battery.

Remedy

Charge battery
up to 8 hours.
Replace with the
same type
of battery.

Press the power
switch again.

Verify that the
load matches the
UPS capability
specified in the
specs.

Remove some
noncritical load.

Charge battery
16 hrs. or more.

Replace with the
same type of
battery.

TROUBLESHOOTING

Use the table below to solve minor UPS 
installation or operation problems. If any 
abnormal situation occur that are not 
listed above, please call service people 
immediately.