6
FURNACE INSTALLATION
Dimension
Inch
mm
A
Backwall to Furnace
29
737
B
Sidewall to Furnace
15
381
C
Sidewall to Flue
18
458
D
Backwall to Flue
18
458
E
Supply Duct (
fi
rst 6 feet)
6
153
F
Supply Duct (after
fi
rst 6 feet)
1
26
G
Minimum Duct height
8
204
INSTALLATION OPTIONS
The installation of this furnace includes supplying electrical power, return (fresh air) ductwork, and supply air
ductwork. This furnace may be installed in two different con
fi
gurations.
1)
Stand alone wood furnace
2)
Add-on wood furnace
See kit installation section in this manual to ensure proper assembly, installation and operation of your new
furnace.
If installing in an area with a fan it should not be allowed to create negative pressure in the room where the
furnace is installed.
LOCATING YOUR FURNACE
(INSURE THAT THE REQUIRED MAINTENANCE CLEARANCES ARE MAINTAINED)
Your furnace must be installed as shown in this manual and in compliance with all local and national codes.
It is of the utmost importance that the clearances to combustible materials be strictly adhered to during installation
of the furnace. Refer to the table and diagrams below for minimum required clearances.
Back
wall
/
A
rrièr
e
M
ur
Ceiling / Plafond
E
F
G
D
Back wall / Arrière Mur
Side wall / P
a
roi Lat
é
rale
C
B
A
CLEARANCE TO COMBUSTIBLES
CLEARANCE TO COMBUSTIBLES