Ashland AGP200 Series Operation, Performance, Specifications And Parts Manual Download Page 5

Receiving Inspection

Upon receiving the pump, it should be inspected for 

damage or shortages. If damage has occurred, file a claim 

immediately with the company that delivered the pump. 

If the manual is removed from the packaging, do not lose 

or misplace.

 

Storage

Any product that is stored for a period longer than six (6) 

months from the date of purchase should be bench

tested prior to installation. A bench test consists of, 

checking the impeller to assure it is free turning and a run

test to assure the motor (and switch if provided) operate 

properly. Do not pump out of liquid. 

IMPORTANT!

 A clearance under the pump for 

entrance of sewage solids must be a minimum of 3 

inches to a maximum of 4.5 inches.

Submergence

The pump should always be operated in the submerged 

condition. The minimum sump liquid level should never 

be less than above the pump’s volute (see fig. 1)

Installation

  

The sump or basin shall be sealed and vented in accor-

dance with local plumbing codes. This pump is designed 

to pump domestic wastewater, nonexplosive and non-

corrosive liquids and shall NOT be installed in locations 

classified as hazardous in accordance with the

National Electrical Code (NEC) ANSI/ NFPA 70 or Cana-

dian Electric Code  

(CEC). The pump  

should never be 

installed in a 

trench, ditch, 

or hole with  

a dirt bottom.

The legs will 

sink into the  

dirt and the  

suction will 

become 

plugged. 

 

 

5

Grinder Pumps

Model: AGP200 Series

Receiving and Installation

Discharge Piping

Install discharge piping or hose assembly to the pump. 

Discharge piping should be as short as possible and sized no 

smaller than the pump discharge. Do not reduce the dis-

charge pipe size below that which is provided on the pump. 

Both a check valve and a shut-off valve are recommended for 

each pump. The check valve is used to prevent backflow into 

the sump. The shut-off valve is used to manually stop system 

flow during pump servicing. Be sure the discharge pipe has a 

1/8” diameter hole approx. 5” from end nearest volute and 

oriented towards the pump body.

Control Panel

Single phase series grinders DO NOT require a control 

panel, but do require a level control with a piggy back plug, 

see“Wiring Connections, page 11”.

 

 

Recommended

Submergence Level

241 [9 1/2

]

Note:

Do not run dry.

FIGURE 1

Motor

 

Single phase motors are provided with heat sensor 

thermostats attached directly to the motor windings. The

thermostats open if the motor windings see excessive 

heat and, in turn, open the motor contactor in the control 

panel when used, breaking the power to the pump. When 

the motor is stopped due to an overheated condition, 

it will not start until the motor has cooled. Three phase 

motors must be used with an appropriate controller with 

integral overload protection.

Motor Seal Failure Warning

    

 

 

The seal chamber is oil filled and provided with moisture 

sensing probes to detect water leakage through the lower 

shaft seal. The probes can also detect moisture present in 

the upper motor housing.
On single phase models, the presence of water energizes 

a red seal leak warning light at the control panel. This is a 

warning light only, and

does not stop the motor. It indicates a leak has occurred 

and the pump must be repaired. Normally, this indicates

the outboard seal has leaked. Allowing the unit to operate 

too long after the warning could cause upper seal

leakage along with motor failure.
The resistance across the moisture sensing (seal failure) 

probes should be checked after a seal leak warning light

has lit. This can be done by disconnecting the black and 

white control wires from the control panel, and measuring 

the resistance with an ohmmeter between the wires.
The reading should be 100,000 ohms or greater. If the 

measured values are below those indicated above, then 

the pump may have a lower seal failure and require service.

Note:

 Failure to use proper circuitry and to connect the 

motor overheat protection in the control panel would 

negate all warranties.

Motor power cord, control cord and cord cap

Assembly 

Each motor power cord has 4 conductors: white, black, 

red and green.
For three phase motors the red, black and white conduc-

tors connect to the three line leads, and the green is con-

nected to a good ground. Interchanging any two line leads 

will reverse the rotation of the motor  

(see Figure 7, page 11)

Minimum Submergence 

Level (Intermittant only)

Summary of Contents for AGP200 Series

Page 1: ...cture which ever comes first Obligation under this warranty is limited to repairing or replacing any part thereof which shall within one year be returned to us with transportation charges prepaid and...

Page 2: ...contact with pumped fluid is possible Risk of electrical shock To reduce risk of electrical shock always disconnect pump from power source before handling Lock out power tag 2 Grinder Pumps Model AGP2...

Page 3: ...Note All dimensions have a tolerance of 1 8 DESCRIPTION To reduce domestic sewage to finely ground slurry PHYSICAL DATA Discharge Size 1 1 4 NPT Impeller Type 10 Vane Vortex Brass Cable Length 35 LIQU...

Page 4: ...9169 MARS 11068 MARS 12248 AGP200M6 35 2 60 208 3 20A 230V 3450 13 G SOW 12 AWG 65 N A N A N A AGP200M2 35 2 60 230 1 20A 230V 3450 17 G SOW 12 AWG 6 MARS 19169 MARS 11068 MARS 12248 AGP200M2E 35 2 60...

Page 5: ...DO NOT require a control panel but do require a level control with a piggy back plug see Wiring Connections page 11 Recommended Submergence Level 241 9 1 2 Note Do not run dry FIGURE 1 Motor Single ph...

Page 6: ...he epoxy potting in the plate between the motor housing and cord cap and is connected to terminal 5 on the relay The black lead exits the potting and is connected to black power cord line via a butt c...

Page 7: ...ticles Milky white oil indicates the presence of water Oil level should be just above the motor when pump is in vertical position Oil Testing Drain oil into a clean dry container by placing pump on it...

Page 8: ...reate a hazard Overfilling oil voids warranty Before any service work is done disconnect and lock out electrical power to pump Cutter Disassembly Lay pump on its side and remove the cutter retaining s...

Page 9: ...ousing 16 being sure o ring 12 is not twisted and in the groove Place four capscrews 14 through holes in seal housing and into seal plate and torque to 6 5 ft lbs Outer Seal Clean and oil stationary s...

Page 10: ...re usually installed in concrete or fiber glass basins with the lift out rail system Figure 5 shows pump mounted on the rail system Instructions for install ing rail system are furnished with rail pac...

Page 11: ...make the installations 2 Three phase pumps instructions for wiring to control panel will be included with control panel All wires should be checked for shorts to ground with an ohmmeter or megger afte...

Page 12: ...e for proper instalation and freedom of operation 7 Discharge head may be too high 7 Check elevation Red light comes on 1 This indicates some water has leaked 1 Change oil in seal chamber at control b...

Page 13: ...emove and examine clogged causing low pump flow valves for proper Installation and freedom of operation 5 Pump may be air locked 5 Loosen union slightly to allow trapped air to escape Verify that turn...

Page 14: ...44 45 44 46 47 49 39 13 NOTE 1 44 45 46 47 48 49 are optional 2 23 24 25 26 27 28 29 30 single phase models with integral capacitors and relay only 3 19 21 22 37 are optional Single Phase model or th...

Page 15: ...USING ASSY 091AGP219 091AGP220 091AGP220 091AGP244 091AGP220 1 20 WAVE WASHER 6203 091AGP221 091AGP221 091AGP221 091AGP221 091AGP221 1 TERMINAL CONNECTOR CE 8 1Ph Model 208 230V 091AGP222 091AGP222 3...

Page 16: ...16 1899 Cottage Street Ashland Ohio 44805 Telephone 855 281 6830 Fax 877 326 1994 ashlandpump com P U M P H o n e s t P r o f e s s i o n a l D e p e n d a b l e AP AGP200 OM 5 2016...

Page 17: ...primero Obligaci n bajo esta garant a se limita a reparar o reemplazar cualquier parte del mismo que ser dentro de un a o ser devuelto a nosotros con cargos de transporte propagados y result ser defec...

Page 18: ...go El c trico Nacional y todos los c digos estatales y locales apli cables Los requisitos pueden variar dependiendo del uso y ubicaci n La instalaci n y servicio es que ser realizado por personal cual...

Page 19: ...cos SiC Cojinete superior 6203 Cojinete inferior 3207 Contacto angular 584 1 2 23 288 3 4 1 1 1 4 NPT FLANGE 8 1 4 3 8 95 3 3 4 584 1 2 23 288 3 4 11 3 8 206 8 1 8 153 1 4 6 103 4 1 1 4 NPT FLANGE 8 1...

Page 20: ...MARS 11068 MARS 12248 AGP200M6 35 2 60 208 3 20A 230V 3450 13 G SOW 12 AWG 65 N A N A N A AGP200M2 35 2 60 230 1 20A 230V 3450 17 G SOW 12 AWG 6 MARS 19169 MARS 11068 MARS 12248 AGP200M2E 35 2 60 230...

Page 21: ...l con un enchufe de leng eta consulte Conexiones de cableado p gina 11 Motor Los motores de la fase solos son proporciona con termosta tos sensor de calor conectados directamente a los devana dos del...

Page 22: ...re la tapa de la caja del motor y el cable y se conecta al terminal 5 en el rel El conductor negro sale de la maceta y se conecta a la l nea de cable de ali mentaci n negro a trav s de un conector de...

Page 23: ...bomba est en posici n vertical Pruebas de Petr leo Vaciar el aceite en un recipiente limpio y seco colocando la bomba en su lado Retire el tap n del tubo 15 desde la caja 19 Verifique el aceite de co...

Page 24: ...puede destruir la bomba y crear un peligro Aceite de sobrellenado anula la garant a Antes de cualquier trabajo de manten imiento se realiza desconecte y bloquee la energ a el ctrica a la bomba Desmon...

Page 25: ...el par a 6 5 pies libra Sello exterior Limpie y aceite estacionaria cavidad del sello en la placa de estanqueidad Deslice herramienta gu a sello sobre el eje del motor Engrase ligeramente No utilice g...

Page 26: ...en las cuencas de hor mig n o de fibra de vidrio con el sistema ferroviario de troquelado La Figura 5 muestra la bomba montada en el sistema ferroviario Las instrucciones para instalar sistema ferrov...

Page 27: ...icados deben hacer las instalaciones 2 Bombas trif sicas instrucciones para el cableado al panel de control se incluir n con el panel de control Todos los cables deben ser revisados para cortos a tier...

Page 28: ...ontrol box completely down on handle may be damaged by lightning then back to ON position If breaker trips again in a few seconds check motor for lighting damage 1 El impulsor de la bomba puede ser ai...

Page 29: ...eraci n 5 Afloje la uni n ligeramente para permitir que el aire atrapado escape Verifique que el nivel de corte del interruptor se ajusta de modo que la cavidad del rotor siempre se inunda Limpiar el...

Page 30: ...44 46 47 49 39 13 NOTE 1 44 45 46 47 48 49 are optional 2 23 24 25 26 27 28 29 30 single phase models with integral capacitors and relay only 3 19 21 22 37 are optional Single Phase model or three Pha...

Page 31: ...91AGP234 1 31 TERMINAL CONNECTOR 2 091AGP235 091AGP235 1 32 SCREW 3 8 16UNC 2 091AGP236 091AGP236 091AGP236 091AGP236 091AGP236 4 33 CORD CAP 091AGP237 091AGP237 091AGP237 091AGP237 091AGP237 1 34 WAS...

Page 32: ...32 1899 Cottage Street Ashland Ohio 44805 Tel fono 855 281 6830 Fax 877 326 1994 ashlandpump com P U M P H o n e s t P r o f e s s i o n a l D e p e n d a b l e AP AGP200 OM 5 2016...

Page 33: ...es graves MARKS AND MEANING AVERTISSEMENT Cette pompe est garantie exempt des d fauts de mat riaux et de fabrication et effectuer au sein des sp cifications applicables pour une p riode d une ann e la...

Page 34: ...les blessures ou la mort r sultant du non respect de ces consignes de s curit l abus ou mauvaise utilisation de pompes ou de l quipement Tous les produits retourn s doivent tre nettoy s d sinfect s ou...

Page 35: ...Taille de d charge 1 1 4 NPT Type de l Impelleur 10 Pale Tourbillon Laton Longueur du C ble 35 MANIPULATION DE LIQUIDE Taille des Solides 1 2 Temp rature du Liquid Maximal 140 F Intermittent 104 F Co...

Page 36: ...169 MARS 11068 MARS 12248 AGP200M6 35 2 60 208 3 20A 230V 3450 13 G SOW 12 AWG 65 N A N A N A AGP200M2 35 2 60 230 1 20A 230V 3450 17 G SOW 12 AWG 6 MARS 19169 MARS 11068 MARS 12248 AGP200M2E 35 2 60...

Page 37: ...ez pas la taille du tuyau de d charge inf rieur celui qui est pr vu sur lapompe Les deux un clapet d anti retour et une vanne d arr t sont recommand s pour chaque pompe Moteur Chaque moteur est fourni...

Page 38: ...eur Pompes de Broyeuse Mod le AGP200 R ception et Installation Pour le monophas la c ruse sort de l enrobage poxy dans la plaque entre le carter du moteur et le bouchon de cordon et est reli e la born...

Page 39: ...che inspectez visuellement l huile dans le carter 19 pour vous assurer qu il est propre et claire ambre p le et exempte de particules en suspension L Huile blanche laiteuse indique la pr sence d eau L...

Page 40: ...gereuse qui peut d truire la pompe et cr er un risque L Huile remplissage excessif annule la garantie Avant tout travail de service est fait d connectez et ver rouillez l alimentation lectrique la pom...

Page 41: ...ue l anneau d O 12 ne soit pas tordu et dans la gorge Placez les quatre vis 14 travers des trous dans le bo tier d tanch it et dans la plaque d tanch it et le torque 6 5 ft lbs Joint Ext rieur Nettoye...

Page 42: ...ns le puisard Ces pompes sont g n ralement install es dans des bas sins en b ton ou en fibre de verre avec le syst me du railde levage La figure 5 mentre la pompe mont e sur le syst me du rail Les ins...

Page 43: ...ohmm tre ou m gohmm tre apr s que les connexions sont faites Cela est IMPORTANT comme un fil de mise la terre peut provoquer une d faillance de la pompe le panneau de contr le ou des blessures 208 23...

Page 44: ...amaged by lightning then back to ON position If breaker trips again in a few seconds check motor for lighting damage Pompes de Broyeuse Mod le AGP200 Meurtre de Probl me ATTENTION 1 impelleur de la po...

Page 45: ...umul autour des flotteurs provo quant que la pompe ne fonctionne pas correctement 1 Passez l op rateur automa tique 2 D connectez le contr le de niveau R glez l ohmm tre pour une gamme basse telle que...

Page 46: ...4 46 47 49 39 13 NOTE 1 44 45 46 47 48 49 are optional 2 23 24 25 26 27 28 29 30 single phase models with integral capacitors and relay only 3 19 21 22 37 are optional Single Phase model or three Phas...

Page 47: ...CONNECT CORD 2 091AGP232 091AGP232 1 29 RING 2 091AGP233 091AGP233 1 30 RUN CAPACITOR 091AGP234 091AGP234 1 31 TERMINAL CONNECTOR 2 091AGP235 091AGP235 1 32 SCREW 3 8 16UNC 2 091AGP236 091AGP236 091AG...

Page 48: ...48 1899 Cottage Street Ashland Ohio 44805 T l phone 855 281 6830 Fax 877 326 1994 ashlandpump com P U M P H o n n t e P r o f e s s i o n n e l F i a b l e AP AGP200 OM 5 2016...

Reviews: