Applicable to: 

GC52

 

 

PROGRAMMING USER DEFINED FLOW RATE UNITS ON THE GC52 
DIFFERENCIALPRESSURE TRANSMITTER 
 
 
 

 

The GC52 differential pressure transmitter is compact and flexible 
instrument often used in flow measurements and volume applications. It 
can be easily programmed with user defined units to display flow rate in 
Gallons Per Minute (GPM) and volume in gallons. 

 
 
 

 

Figure 1 – GC52 Differential Pressure Transducer 

 
 

Water Flow Rate and Volume Application: 

 
This example demonstrates the use of GC52 differential pressure transmitter to measure and control 
flow rate in GPM. Also, to switch from flow rate reading to volume, automatic or manual. Although, the 
GC52 differential pressure transmitter can be purchase with several ranges, for this application a 
transmitter with 0 to 40 IWC pressure range has been selected. As well, an orifice plate with 2.40” bore, 
an eight-inch line diameter pipe and a variable frequency water pump. The transmitter shall provide the 
analog output to the variable frequency water pump. The variable frequency water pump uses the 4-
20mA input to control the amount of energy sent to the pump to slow down or speed up the pump to 
maintain a constant flow of 65 GPM. 

 
 
 
 
 
 
 
 
 

 

Summary of Contents for GC52

Page 1: ...C52 Differential Pressure Transducer Water Flow Rate and Volume Application This example demonstrates the use of GC52 differential pressure transmitter to measure and control flow rate in GPM Also to...

Page 2: ...com info ashcroft com 1 800 328 8258 Rev A 02 17 Page 2 of 8 Figure 2 GC52 Flow Rate Diagram Example Figure 3 GC52 Installation Example Installation Remove the lid from the transmitter by turning it c...

Page 3: ...ow and integrated Volume Program Guidelines Below is an Illustration to program the transmitter in GPM and integrated volume in gallons as the arbitrary units Proceed to scale down the transducer rang...

Page 4: ...play n rot Press and release M button to select and move to the next step Step 3 P 20 0 To enter the maximum differential pressure corresponding to the maximum flow rate 88 GPM This is the orifice pla...

Page 5: ...next step Step 8 _ _ _ _ A 100 0 To enter span analog output reference corresponding to 20 mA The operational range is from 0 to 88 GPM of water Therefore 100 full span is selected as the span or 20 m...

Page 6: ...p Step 12 C 0 0 Loop check mode allows program and analog output verification with the transmitter pressurized or non pressurized It simulates the process and allows for troubleshooting Press Up or Do...

Page 7: ...com info ashcroft com 1 800 328 8258 Rev A 02 17 Page 7 of 8 Analog output terminal check When the front cover is removed the analog output check terminals CH and CH are visible at the upper part of...

Page 8: ...g measurement mode or loop check see results below for reference Connect amp meter per manual instructions or figure above Press the Down arrow until 0 0 GPM is displayed or apply 0 IWC Verify amp met...

Reviews: