Step 

 

 

 

L   0.0

 To enter low-cut to flow rate. It forces display to zero and 

analog output to 4 mA. 

 

Low-cut shall not be used on this application, constant flow rate 
shall be maintained. 

 

Press Up or Down arrow until 0.0 is selected. 

 

 Press and release M button to select and move to the next step. 

 
 

 

 
 
 
 

Step 

 

 

A    0.0  

To enter analog output zero reference corresponding to 4 

mA. 

 

The operational range is from 0 to 88 GPM of water. Therefore, 
select 0% FS or 4mA analog output. 

 

Press Up or Down arrow until 0.0 is displayed. That, is the analog 
output at 0% FS (4mA at 0 GPM of water).  

 

Press and release M button to select and move to the next step 

 

 

 
 
 
 

Step 

         
              

  _ _ _ _ 

 

A 100.0 

To enter span analog output reference corresponding to 20 

mA. 

 

The operational range is from 0 to 88 GPM of water. Therefore, 
100% full span is selected as the span or 20 mA analog output. 

 

Press UP or Down arrow until 100.0 is displayed. That, is the analog 
output at 100% FS (20mA at 88 GPM).  

 

Press and release M button to select and move to the next step. 

 

 

 
 
 

Step 

 
 

 

U    n̅ in

 To enter time factor. When flow rate is GPM, minutes shall 

be selected as the same time factor. 

 

Press UP or Down arrow until “n̅ in” is displayed. That, is the time 
factor corresponding to minutes.  

 

Press and release M button to select and move to the next step. 
 

 

 
 
 

Step 

10 

 

U _  _ 1

 To enter Flow rate volume factor. When flow rate is GPM, 1 

shall be selected to match flow factor units of gallons X1. 

 

Selectable options 1,10, 100 and 1000. 

 

1 shall be selected since the arbitrary units are in gallons. 

 

Press UP or Down arrow until “1” is displayed. That, is the unit factor 
corresponding to gallons.  

 

Press and release M button to select and move to the next step. 
 

 

Summary of Contents for GC52

Page 1: ...C52 Differential Pressure Transducer Water Flow Rate and Volume Application This example demonstrates the use of GC52 differential pressure transmitter to measure and control flow rate in GPM Also to...

Page 2: ...com info ashcroft com 1 800 328 8258 Rev A 02 17 Page 2 of 8 Figure 2 GC52 Flow Rate Diagram Example Figure 3 GC52 Installation Example Installation Remove the lid from the transmitter by turning it c...

Page 3: ...ow and integrated Volume Program Guidelines Below is an Illustration to program the transmitter in GPM and integrated volume in gallons as the arbitrary units Proceed to scale down the transducer rang...

Page 4: ...play n rot Press and release M button to select and move to the next step Step 3 P 20 0 To enter the maximum differential pressure corresponding to the maximum flow rate 88 GPM This is the orifice pla...

Page 5: ...next step Step 8 _ _ _ _ A 100 0 To enter span analog output reference corresponding to 20 mA The operational range is from 0 to 88 GPM of water Therefore 100 full span is selected as the span or 20 m...

Page 6: ...p Step 12 C 0 0 Loop check mode allows program and analog output verification with the transmitter pressurized or non pressurized It simulates the process and allows for troubleshooting Press Up or Do...

Page 7: ...com info ashcroft com 1 800 328 8258 Rev A 02 17 Page 7 of 8 Analog output terminal check When the front cover is removed the analog output check terminals CH and CH are visible at the upper part of...

Page 8: ...g measurement mode or loop check see results below for reference Connect amp meter per manual instructions or figure above Press the Down arrow until 0 0 GPM is displayed or apply 0 IWC Verify amp met...

Reviews: