Asentria SiteBoss 530 User Manual
46
Serial Handshaking Alarm Settings
Serial Handshaking Alarms allows the S530 to monitor each of its serial ports and alert you if the DTR signal from
the connected device drops low. This would be an indicator that the connected device has failed, the cable
between the S530 and the device has been disconnected, or a number of other reasons depending on the device.
It can also alert you when the DTR signal goes high again.
SiteBoss 530 - Serial Handshaking Alarm Settings
A) I/O 1 Serial Handshaking Alarms [OFF]
B) I/O 2 Serial Handshaking Alarms [OFF]
I/O n Serial Handshaking Alarms
displays a menu for configuring alarming on serial DTR handshaking
conditions.
I/O n Serial Handshaking Alarms
SiteBoss 530 - I/O 1 Serial Handshaking Alarms
A) Serial Handshaking Low Alarm Enable [OFF]
B) Serial Handshaking Low Alarm Actions []
C) Serial Handshaking Low Alarm Message [Handshake Low]
D) Serial Handshaking Low Alarm Class [Info]
E) Serial Handshaking Low Trap Number [510]
F) Serial Handshaking High Alarm Enable [OFF]
G) Serial Handshaking High Alarm Actions[]
H) Serial Handshaking High Alarm Message[Handshake High]
I) Serial Handshaking High Alarm Class [Info]
J) Serial Handshaking High Trap Number [510]
Serial Handshaking Low / High Alarm Enable
is an ON/OFF toggle to enable alarming on high or low
handshaking levels. Default setting is OFF.
Serial Handshaking Low / High Alarm Actions
displays the Actions List, a menu where the action string for the
alarm is configured. This field will be empty [ ] if no actions have been configured, and will show [*SET*] if one or
more actions have been configured. Refer to
in the Features chapter for more information.
Serial Handshaking Low / High Alarm Message
is the message sent with any text-based action for this event.
Default setting is “Handshake Low/High”. (Max length for each is 126 chars)
Serial Handshaking Low / High Alarm Class
sets the class for the event. When this option is selected, a list of
the classes previously defined in the
is displayed, from which you can select one to be assigned to
this event.
Serial Handshaking Low / High Trap Number
sets the number to be sent with any SNMP traps for this event.
Default is 510, but trap number can also be set in the range of 1000 – 1199 as needed.
CPE Alarm Settings
SiteBoss 530 - CPE Alarm Settings
A) Alarm Enable [OFF]
B) Alarm Actions []
C) Alarm Trap Number [511]
D) Alarm Class [Info]
E) Return to Normal Actions []
F) Return to Normal Trap Number [511]
G) Return to Normal Class [Info]
These settings are only for use with Customer Premises Equipment (CPE) managed via the Asentria SitePath
secure, unified administration portal software. Contact
for further information.
Summary of Contents for SiteBoss 530
Page 6: ......