Asentria SiteBoss 530 User Manual
102
Inactive Alarm Alias
is the same as Active Alarm Alias, but used with Return to Normal events.
Temperature Sensor Setup
Below is a representative Events Menu showing a Type2 EventSensor ES-T to monitor temperature:
SiteBoss 530 - External Temperature Event
Device Number: 2 Device ID: EST000027 Device Name: Test ES-T
A) Temperature Sensor Enabled [OFF]
B) Sensor Values Represented in [FAHRENHEIT]
C) Temperature Deadband [3]
D) Very High Event Settings [100] [] [120] [Info]
E) High Event Settings [80] [] [120] [Info]
F) Return to Normal Settings [-] [] [120] [Info]
G) Low Event Settings [50] [] [120] [Info]
H) Very Low Event Settings [30] [] [120] [Info]
Temperature Sensor Enabled
is an ON/OFF toggle to enable the temperature sensor.
Sensor Values Represented In
toggles either FAHRENHEIT or CELSIUS for the desired temperature scale.
Temperature Deadband
is the range, in degrees, on either side of a temperature setting that prevents the event from
repeatedly going in and out of the "alarm state" as the actual temperature fluctuates above and below the temperature
setting.
Very High / High / Low / Very Low Event Settings
display a menu where the temperature at each level can be
configured to alarm along with the action(s) to occur, trap number, and class. In the case of Very High or High levels,
the alarm will occur as the temperature rises above the setting. In the case of Low or Very Low, the alarm will occur
as the temperature drops below the setting.
displays a menu where the actions to occur when the temperature returns to normal
(drops below the High/Very High settings, or rises above the Low/Very Low settings) can be configured.
Very High / High / Low / Very Low Event Settings Setup
SiteBoss 530 - External Temperature Event Settings
Device Number: 2 Device ID: EST000027 Device Name: Test ES-T
A) Very High Event Temperature [100]
B) Very High Event Actions []
C) Very High Event Trap Number [120]
D) Very High Event Class [Info]
The menu for setting Very High Temperature settings is shown. Menus for High/Low/Very Low are identical.
Very High Event Temperature
sets the temperature at which the Very High Event Actions will be triggered.
Very High Event Actions
displays the Actions List, a menu where the action string for the event is configured. This
field will be empty [ ] if no actions have been configured, and will show [*SET*] if one or more actions have been
configured. Refer to the
for more information.
Very High Trap Number
sets the trap number which can be useful when using SNMP trap managers that employ a
trap numbering system to help identify incoming traps. The default trap number for Temperature Events is 120, but
any number in the alternate range of 1000 – 1199 can be used.
Very High Event Class
sets the class for the event. When this option is selected, a list of the classes previously
is displayed, from which you can select one to be assigned to this event.
Summary of Contents for SiteBoss 530
Page 6: ......